beautypg.com

5 rtu framing, Rtu framing, Table 5.10 – RLE LD5200 V.2.3 User Manual

Page 100: Query sample, Table 5.11, Response sample

background image

100

LD5200 User Guide

800.518.1519

5

Modbus Communication

5.5 RTU

Framing

The example below shows a typical Query/Response from the LD5200 module.

Slave address 2 responds to Function Code 4 with 6 bytes of hexadecimal data and ends with

CRC16 checksum

Register Values:

40001 = 0000 (hex)

40002 = 0000 (hex)

40003 = 0001 (hex)

Slave

Address

Function

Code

Starting

Register

“Msb”

Starting

Register

“Lsb”

Numbers

of

Registers

“Lsb”

Number of

Registers

“Lsb”

CRC 16

“Lsb”

CRC

“Msb”

02

04

00

00

00

03

B5

A3

Table 5.10

Query Sample

Slave

Address

Function

Code

Count

Bytes of

Data

Register

Data

Msb Lsb

Register

Data

Msb Lsb

Register

Data

Msb Lsb

CRC 16

“Lsb”

CRC 16

“Msb”

02

04

06

00

00

00 00

00 01

B5

A3

Table 5.11