Technical Specifications

EIA-485

Modbus RTU, Master & Slave; BACnet MS/TP; N2, Slave

EIA-232

Terminal emulation, VT100 compatible

RJ-45

Ethernet, TCP/IP; Modbus/TCP/UDP, Master & Slave;

SNMP V1, V2, V3, NTP, SMTP, DNS; BACnet/IP

Alarm Notification

Audible Alarm

85dBA @ 2ft (0.6m); re-sound 0-999min.

Visible Alarm

Alarm indicated on LCD touch screen and through web

interface

Logging Capabilities

Logs are downloadable to .txt file

Alarm History/Event Log

Last 1,024 events

Trend Log

Cable current level every day, for the last 365 days

Login Security

LCD Touch Screen

No password required to view controller status and data.

Administrator password limits access to configuration

options.

Web Interface

Username and password can be configured.

Front Panel Interface

Display

480 x 272 pixel color backlit LCD touch screen;
95.04mm x 53.85 mm

Operating Environment

Temperature

32° to 122°F (0° to 50°C)

Humidity

5% to 95% RH, non-condensing

Altitude

15,000ft (4,572m) max.

Storage Environment

-4° to 185°F (-20° to 85°C)

Dimensions

12.5"W x 10"H x 3.25"D
(318mmW x 254mmH x 83mmD)

Weight

8.2 lbs. (3.7kg)

Mounting

Type 1 wall mount enclosure

Certifications

CE; ETL listed: conforms to UL 61010-1, EN 61010-1;

certified to CSA C22.2 NO. 61010-1; RoHS compliant

Table F.1 Technical Specifications (continued)