Technical Specifications
EIA-485
Modbus RTU, Master & Slave; BACnet MS/TP; N2, Slave
EIA-232
Terminal emulation, VT100 compatible
RJ-45
Ethernet, TCP/IP; Modbus/TCP/UDP, Master & Slave;
SNMP V1, V2, V3, NTP, SMTP, DNS; BACnet/IP
Alarm Notification
Audible Alarm
85dBA @ 2ft (0.6m); re-sound 0-999min.
Visible Alarm
Alarm indicated on LCD touch screen and through web
interface
Logging Capabilities
Logs are downloadable to .txt file
Alarm History/Event Log
Last 1,024 events
Trend Log
Cable current level every day, for the last 365 days
Login Security
LCD Touch Screen
No password required to view controller status and data.
Administrator password limits access to configuration
options.
Web Interface
Username and password can be configured.
Front Panel Interface
Display
480 x 272 pixel color backlit LCD touch screen;
95.04mm x 53.85 mm
Operating Environment
Temperature
32° to 122°F (0° to 50°C)
Humidity
5% to 95% RH, non-condensing
Altitude
15,000ft (4,572m) max.
Storage Environment
-4° to 185°F (-20° to 85°C)
Dimensions
12.5"W x 10"H x 3.25"D
(318mmW x 254mmH x 83mmD)
Weight
8.2 lbs. (3.7kg)
Mounting
Type 1 wall mount enclosure
Certifications
CE; ETL listed: conforms to UL 61010-1, EN 61010-1;
certified to CSA C22.2 NO. 61010-1; RoHS compliant
Table F.1 Technical Specifications (continued)