beautypg.com

Modbus communication, 1 comm port settings, 2 leak detection modbus master – RLE LD5200 V.2.3 User Manual

Page 85: 1 connect distance read panels to the ld5200, Comm port settings leak detection modbus master, Connect distance read panels to the ld5200, Odbus, Ommunication

background image

rletech.com

LD5200 User Guide

85

C

H A P T E R

C

HAPTER

0

M

ODBUS

C

OMMUNICATION

5.1

Comm Port Settings

The Modbus/EIA-485 Configuration Menu allows users to configure all three of the LD5200’s

EIA-485 Modbus ports. The LD5200 is configurable as a both a Modbus master and a Modbus

slave device. As a slave device, the LD5200 can have only one master. All three ports may

have their addresses and baud rates set in this menu. All addresses may be different and can be

configured from 0 (disabled) to 254. Baud rates can be different and can be configured as 9600

(default), 19200, or 38400. Settings can be configured through both the LCD and the web

interface.

The Leak Detection Master option enables slave units to activate the LD5200 when they are

triggered into an alarm state. This function is beneficial when the LD5200 is a remote system

that does not have personnel in the immediate vicinity to monitor the alarm status.

When using the leak detection master option, the LD5200 relays can be activated according to

the slave unit alarm. If the slave has a leak alarm or a cable break alarm, the LD5200 leak or

cable relay will change state, respectively (i.e. it will trigger that an alarm is present). The zone

will then appear on the LCD and an alarm state will be reported to the top level of the system.

5.2

Leak Detection Modbus Master

This feature allows the LD5200 to act as a Modbus master, so it can talk to other RLE distance

read panels. The system status can be viewed by using the view zones menu. The LD5200 will

display leak, cable break, cable contamination, and loss of communications alarms from the

slave units connected to it.

5.2.1 Connect Distance Read Panels to the LD5200

Using a two wire configuration, connect the slave units in a 485 daisy chain. You will have to

set the EIA-485 slave address in each Leak detection unit. The first unit connected must be set

to address 2. The following units will increase in numeric order by one unit (e.g., the next unit

would be set to address 3, the following would be set to address 4, etc.; see Figure 5.1.)