beautypg.com

1 tb1: 4-20ma output, 2 tb2: sensing cable interface, 3 tb3: maintenance relay – RLE LD5200 V.2.3 User Manual

Page 18: 4 tb4: two fault/leak relay outputs, Figure 2.3, Cable connection tb2

background image

18

LD5200 User Guide

800.518.1519

2

Installation

2.3.1 TB1:

4-20mA

Output

The 4-20mA analog output allows the LD5200 to communicate with a 4-20mA loop powered

output. This connection is provided on TB1. The maximum range (20 mA) can be set to 1000,

2500, or 5000 feet. Connect the 4-20mA wires to TB1 as follows:

TB1-1 4-20mA positive (+)

TB1-2 4-20mA negative (-)

2.3.2 TB2: Sensing Cable Interface

A 15-foot (4.57m) section of non-sensing cable is supplied with each LD5200. The leader

cable connects sensing cable to the LD5200, since sensing cable cannot connect directly to the

unit. Insert its four stripped wires into the appropriate slots in TB2 - from left to right: white,

black, green and red.

Figure 2.3

Cable Connection TB2

NOTE If the terminal connector is removed from the end of the cable, make sure the wires are in the

same order, W - B - G - R, when the connector is reapplied.

For further information regarding sensing cable, refer to

“Connect the SeaHawk Sensing

Cable” on page 21

.

2.3.3 TB3: Maintenance Relay

Maintenance reminders can be configured through the LCD or the web interface. This relay

(TB3) is activated once the scheduled maintenance period has lapsed. If you wish, connect this

relay output to a BMS or NMS to monitor regularly scheduled maintenance intervals.

2.3.4 TB4: Two Fault/Leak Relay Outputs

TB4 houses two Form C relay outputs. These relays provide alarm notification when a leak,

cable fault, or cable contamination is detected.

The top row of TB4 (pins 1 - 6) provides a connection to one of the leak alarm relay outputs

and one of the fault relay outputs; the bottom row of TB5 (pins 7 - 12) provides a second set of

contacts for the same leak and fault alarms.

TB2-1 White wire

TB2-2 Black wire

TB2-3 Green wire

TB2-4 Red wire