beautypg.com

20ma output testing, Figure e.1, 20ma testing – RLE LD5200 V.2.3 User Manual

Page 115: Utput, Esting

background image

rletech.com

LD5200 User Guide

115

A

P P E N D I X

C

HAPTER

0

4-20

M

A O

UTPUT

T

ESTING

The LD5200’s 4-20mA output is loop powered and tested by the manufacturer. The

manufacturer guarantees its performance upon delivery. Should the 4-20mA output need to be

tested in the field, follow these steps. The following procedure is performed with the cable

connected, unless otherwise indicated.

1

Turn off all power to the LD5200

2

Remove the two position plug from TB1.

3

Remove any wires from the terminal and

install a 200Ohm resistor to TB1-2 (-).

Then apply +24V (TB7-2) to TB1-1 (+)

and ground (TB7-1) of the 24V supply to

the other side of the resistor.

4

Reinstall the plug on TB1.

5

Reapply power to the LD5200.

6

With the system on and no alarms present,

measure the DC voltage across the

resistor. A value of 0.8VDC or 1.0VDC

should register. This equates to 4mA 0r

5mA (depending on the LD5200’s

configuration), or normal operation.

7

Remove the SeaHawk Leak Detection Cable (SC) and wait for the unit to activate its cable

trouble alarm. Measure the DC voltage across the resistor. A value of approximately

3.8VDC or 4.0VDC should be measured. This equates to 19mA or 20mA (depending on the

LD5200’s configuration), or a fault alarm. Reconnect the SC cable.

8

Place water on the end of the SC cable. Measure the DC voltage across the resistor. The

value will be proportional to the length of cable measured by the LD5200 and scaled

according to the range setting. Dry the cable.

9

Place water on the start of the cable. Measure the DC voltage across the resistor. A

measurement of approximately 0.8VDC or 0.9VDC, or 4mA or 5mA (both depending on

the LD5200’s configuration), should be measured. This corresponds to a leak at zero

distance. Dry the cable.

Figure E.1

4-20mA Testing

TB1

TB7