3 slave controller, Slave controller, Figure 4.7 – RLE LD5200 V.2.3 User Manual
Page 55: Table 4.3, Slave controller configuration options
![background image](https://www.manualsdir.com/files/802966/content/doc055.png)
rletech.com
LD5200 User Guide
55
4
Web Interface
4.3.3 Slave
Controller
The LD5200 can act as a Modbus or Bacnet IP master for other RLE leak detection devices.
Up to 127 slave devices can be connected to one LD5200. To configure the LD5200 as a
Modbus master, refer to Chapter 5, “Modbus Communication” on page 85.
Figure 4.7
Slave Controller Configuration Page.
Option
Description
Jump to Page
Use this drop down menu to access additional devices.
Controller #
A fixed number, 1 - 127, used to designate the controller.
Label
Type a descriptive label for the controller, 30 characters or less.
Control Type
Designate the slave device as distance read or zone
Enable Comm Type
Select a communications type for the slave device:
Disabled
EIA-485 Port1
EIA-485 Port2
EIA-485 Port3
Modbus/TCP
Modbus/UDP
Bacnet/IP
Address/Slave ID/
Device ID
Designate the Slave ID or Device ID.
IP Address
Enter the IP Address of the slave device
Table 4.3
Slave Controller Configuration Options