LCD Touch Screen Interface

3.5.7 EIA-485 / Modbus / N2

If the LD5200 will be

communicating via the EIA-485

port, configure the necessary options

here.

Menu selections are as follows:

Option

Description

TCP/UDP UID

Set the TCP/UDP unique identifier. this will be a value

between 1 and 254. A value of 0 disables this option.

Alarm Relay

Enable or disable the alarm relay.

EIA-485 Port 1

Select Modbus-Slave or Modbus-Master

Port 1 Baud Rate

Selectable: 9600, 19200, or 38400

Port 1 Slave Address

Set the slave address, 1-254. 0 = disabled.

EIA-485 Port 2

Select Modbus-Slave, Bacnet Ms/Tp Slave, Modbus-

Master, or N2 (fixed, 9600, n,1)

Port 2 Baud Rate

Selectable: 9600, 19200, or 38400

Port 2 Slave Address

Set the slave address, 1-254. 0 = disabled.

EIA-485 Port 3

Select Modbus-Slave or Modbus-Master

Port 3 Baud Rate

Selectable: 9600, 19200, or 38400

Port 3 Slave Address

Set the slave address, 1-254. 0 = disabled.

Table 3.16

LCD EIA-485 / Modbus / N2 Setup - Configurable Options

LCD - EIA485/Modbus/N2 Setup Menu