3 slave zone, Slave zone, Table 3.12 – RLE LD5200 V.2.3 User Manual

Page 41: Lcd slave zones setup - configurable options

background image

rletech.com

LD5200 User Guide

41

3

LCD Touch Screen Interface

3.5.3 Slave

Zone

Slave zones are secondary physical

controllers that report to the LD5200.

Zone controllers and distance-read

controllers can be networked as

slaves to a master LD5200. Up to 128

slave devices can report to one

LD5200.

Option

Description

Slave Zone #

Non-editable; defined by the blue highlighted device you chose

to configure.

Label

Enter a name for the slave controller, 30 characters or less.

Controller Type

Designate the slave device as zone or distance read

Comm Type

Select a communications type for the slave device:
Comms Disabled
EIA-485 port 1
EIA-485 Port 2
EIA-485 Port 3
Modbus/TCP
Modbus/UDP
Bacnet/IP

Slave ID

Designate the Slave ID or Device ID

IP Address

Enter the IP Address of the slave device.

V-Zone

Label the virtual zones. A device communicating via Modbus

will have editable zone names and end distances. A device

communicating via Bacnet will be read-only - the LD5200 will

obtain the information from the other controller.

Table 3.12

LCD Slave Zones Setup - Configurable Options

LCD - Slave Zone Settings Menu

LCD - Slave Zone Setup Menu - Bacnet

LCD - Slave Zone Setup Menu- Modbus