3 slave zone, Slave zone, Table 3.12 – RLE LD5200 V.2.3 User Manual
Page 41: Lcd slave zones setup - configurable options
![background image](https://www.manualsdir.com/files/802966/content/doc041.png)
rletech.com
LD5200 User Guide
41
3
LCD Touch Screen Interface
3.5.3 Slave
Zone
Slave zones are secondary physical
controllers that report to the LD5200.
Zone controllers and distance-read
controllers can be networked as
slaves to a master LD5200. Up to 128
slave devices can report to one
LD5200.
Option
Description
Slave Zone #
Non-editable; defined by the blue highlighted device you chose
to configure.
Label
Enter a name for the slave controller, 30 characters or less.
Controller Type
Designate the slave device as zone or distance read
Comm Type
Select a communications type for the slave device:
Comms Disabled
EIA-485 port 1
EIA-485 Port 2
EIA-485 Port 3
Modbus/TCP
Modbus/UDP
Bacnet/IP
Slave ID
Designate the Slave ID or Device ID
IP Address
Enter the IP Address of the slave device.
V-Zone
Label the virtual zones. A device communicating via Modbus
will have editable zone names and end distances. A device
communicating via Bacnet will be read-only - the LD5200 will
obtain the information from the other controller.
Table 3.12
LCD Slave Zones Setup - Configurable Options
LCD - Slave Zone Settings Menu
LCD - Slave Zone Setup Menu - Bacnet
LCD - Slave Zone Setup Menu- Modbus