Table 5.3, Output registers – RLE LD5200 V.2.3 User Manual
Page 88
![background image](https://www.manualsdir.com/files/802966/content/doc088.png)
88
LD5200 User Guide
800.518.1519
5
Modbus Communication
Register
Name
Description
Units
Range
40001
Leak Threshold
Trip current for leak alarm
25-295
uAmps
0-65535
40002
Contamination
Threshold
Trip current for contamination alarm
20-295
uAmps
0-65535
40003
Spare
0-65535
40004
Spare
0-65535
40005
Spare
0-65535
40006
Spare
0-65535
40007
Spare
0-65535
40008
Spare
0-65535
40009
Spare
0-65535
40010
Spare
0-65535
40011
Spare
0-65535
40012
Spare
0-65535
40013
Spare
0-65535
40014
Spare
0-65535
40015
Spare
0-65535
40016
Leak Alarm Delay
Leak Alarm Delay
5-995
seconds
0-65535
40017
Contamination Alarm
Delay
Contamination Alarm Delay
5-995
seconds
0-65535
Table 5.3
Output Registers