Echelon i.LON SmartServer 2.0 User Manual

Page 54

background image

i.LON SmartServer 2.0 Programmer’s Reference

4-13

Response



0

Net/LON/iLON

App/VirtFb/temp_thermostat

Dp_In;xsi:type=“LON_Dp_Cfg”
0
2008-03-14T16:34:11.310-07:00

LonFormat="#0000000000000000[0].SNVT_temp"

Unit="°C">21.0

LonFormat="UCPTvalueDef">OCCUPIED

LonFormat="UCPTpointStatus">AL_NUL

255

Net/LON/iLON

App/VirtFb/nviSwitch

Dp_In;xsi:type=“LON_Dp_Cfg”
0
2008-03-14T16:34:11.340-07:00

0.0 0
0.0
0

LonFormat="UCPTvalueDef">OFF

LonFormat="UCPTpointStatus">AL_NUL

255

Net/LON/iLON

App/VirtFb/nvoSetting

Dp_Out;xsi:type=“LON_Dp_Cfg”
0
2008-03-14T16:34:11.380-07:00

>SET_OFF 0.0 0.00
SET_OFF
>0.0
>0.00

LonFormat="UCPTpointStatus"

>AL_NUL

255



The following table describes the properties of each element returned by the Read function.

Property Description

The name of the data point in the following format:
<network/channel/device/functional block/data point>.

The direction of the data point (Dp_In, Dp_Out, or Dp_In_Out
[unspecified]), and its xsi type, which corresponds to the bus on
which the data point resides (e.g., LON_Dp_Cfg for a L

ON

W

ORKS

data point) . This determines the icon used to represent the data
point in the navigation pane on the left side of the SmartServer
Web interface.