Echelon i.LON SmartServer 2.0 User Manual
Page 54

i.LON SmartServer 2.0 Programmer’s Reference
4-13
Response
App/VirtFb/temp_thermostat
LonFormat="#0000000000000000[0].SNVT_temp" Unit="°C">21.0
LonFormat="UCPTvalueDef">OCCUPIED
LonFormat="UCPTpointStatus">AL_NUL
App/VirtFb/nviSwitch
LonFormat="UCPTvalueDef">OFF
LonFormat="UCPTpointStatus">AL_NUL
App/VirtFb/nvoSetting
LonFormat="UCPTpointStatus" >AL_NUL
The following table describes the properties of each
Property Description
The name of the data point in the following format:
<network/channel/device/functional block/data point>.
The direction of the data point (Dp_In, Dp_Out, or Dp_In_Out
[unspecified]), and its xsi type, which corresponds to the bus on
which the data point resides (e.g., LON_Dp_Cfg for a L
ON
W
ORKS
data point) . This determines the icon used to represent the data
point in the navigation pane on the left side of the SmartServer
Web interface.