beautypg.com

2 visual basic.net examples, Visual basic.net examples -30 – Echelon i.LON SmartServer 2.0 User Manual

Page 382

background image

i.LON SmartServer 2.0 Programmer’s Reference

21-30

21.2

Visual Basic.NET Examples

21.2.1

Reading and Writing Data Point Values in Visual Basic.NET

This VB console example toggles the SmartServer’s digital relay outputs when run. It demonstrates
how to use an xSelect statement to filter items returned by a List() method, and it demonstrates how to
write to data points using values and presets.

You can execute this code after you have referenced and inherited from the SmartServer WSDL as
described in section 20.1, and instantiated and initialized the Web service client as described in section
20.2.3.

For more information on the data point properties set and read in this example, see section 4.3.2,
Using the Get Function on the Data Server
, and section 4.3.3, Using the Read Function on the Data
Server
, respectively.

Module

DpModule


Sub

Main()

'See Section 20.2.3 for more information on iLON_SoapCalls class

Dim

SmartServer

As

iLON_SoapCalls =

New

iLON_SoapCalls

SmartServer.BindClientToSmartServer()

Try


Console.Out.WriteLine(vbNewLine + vbNewLine +

"Reading and Writing DP Values with an xSelect"

+ vbNewLine +

"-------------------------------"

+ vbNewLine)


'we create an xSelect object and then specify the filter to be used

Dim

xSelect

As

iLON_SmartServer.E_xSelect =

New

iLON_SmartServer.E_xSelect

xSelect.xSelect =

"//Item[@xsi:type=""Dp_Cfg""][contains (UCPTname,""nviClaValue"")]"

'Create an ItemColl that stores the objects returned by a List() function that takes our

'

xSelect object

Dim

ItemColl

As

iLON_SmartServer.Item_Coll = SmartServer._iLON.List(xSelect)


'we create an ItemDataColl that stores the objects returned by a Read() function that takes

'

the ItemColl returned by the List()

Dim

ItemDataColl

As

iLON_SmartServer.Item_DataColl = SmartServer._iLON.Read(ItemColl)


'check that there are obejcts in the ItemDataColl

If

(ItemDataColl.UCPTfaultCount > 0)

Then

Console.Out.WriteLine(

"you've got Read errors"

)


Else

Console.Out.WriteLine(

"Reading Data Point Values"

+ vbNewLine)

For

i

As

Integer

= 0

To

ItemDataColl.Item.Length - 1


' we allocate a Item-Data array object to read DP names and values

Dim

dpItems

As

iLON_SmartServer.Dp_Data = ItemDataColl.Item(i)

Console.Out.WriteLine(dpItems.UCPTname +

" = "

+ dpItems.UCPTvalue(0).Value)


If

(dpItems.UCPTvalue(0).Value =

"100.0 1"

)

Then

dpItems.UCPTvalue(0).Value =

"0.0 0"

dpItems.UCPTvalue(1).Value =

"OFF"

ElseIf

(dpItems.UCPTvalue(0).Value =

"0.0 0"

)

Then

dpItems.UCPTvalue(0).Value =

"100.0 1"

dpItems.UCPTvalue(1).Value =

"ON"

End

If