Table 69B — Staged Gas Heat — 48A2,A3,A4,A5 Units

Table 70 — Staged Gas Heat Control Steps (Configuration

HEAT

SG.CF

HT.ST = 1)

Table 71 — Staged Gas Heat Control Steps (Configuration

HEAT

SG.CT

HT.ST = 2)

Table 72 — Staged Gas Heat Control Steps (Configuration

HEAT

SG.CT

HT.ST = 3)

UNIT SIZE

HEAT CAPACITY

UNIT MODEL NO.

POSITION NO. 5

Configuration

HEAT

SG.CF

HT.ST

ENTRY VALUE

020-030

Low

S

1 = 5 STAGE

High

T

2 = 7 STAGE

035-050

Low

S

1 = 5 STAGE

High

T

1 = 5 STAGE

060

Low

S

4 = 11 STAGE

High

T

3 = 9 STAGE

STAGE

RELAY OUTPUT

CAPACITY

%

Heat 1

Heat 2

Heat 3

Heat 4

Heat 5

Heat 6

MBB-RLY8

MBB-RLY7

SCB-RLY1

SCB-RLY2

SCB-RLY3

SCB-RLY4

IGC1

MGV1

IGC2

MGV2

IGC3

MGV3

0

OFF

OFF

OFF

OFF

OFF

OFF

0

1

ON

OFF

OFF

OFF

OFF

OFF

37

2

ON

ON

OFF

OFF

OFF

OFF

50

3

ON

OFF

ON

OFF

OFF

OFF

75

4

ON

ON

ON

OFF

OFF

OFF

87

5

ON

ON

ON

ON

OFF

OFF

100

STAGE

RELAY OUTPUT

CAPACITY

%

Heat 1

Heat 2

Heat 3

Heat 4

Heat 5

Heat 6

MBB-RLY8

MBB-RLY7

SCB-RLY1

SCB-RLY2

SCB-RLY3

SCB-RLY4

IGC1

MGV1

IGC2

MGV2

IGC3

MGV3

0

OFF

OFF

OFF

OFF

OFF

OFF

0

1

ON

OFF

OFF

OFF

OFF

OFF

25

2

ON

ON

OFF

OFF

OFF

OFF

33

3

OFF

OFF

ON

OFF

OFF

OFF

50

4

OFF

OFF

ON

ON

OFF

OFF

67

5

ON

OFF

ON

OFF

OFF

OFF

75

6

ON

ON

ON

OFF

OFF

OFF

83

7

ON

ON

ON

ON

OFF

OFF

100

STAGE

RELAY OUTPUT

CAPACITY

%

Heat 1

Heat 2

Heat 3

Heat 4

Heat 5

Heat 6

MBB-RLY8

MBB-RLY7

SCB-RLY1

SCB-RLY2

SCB-RLY3

SCB-RLY4

IGC1

MGV1

IGC2

MGV2

IGC3

MGV3

0

OFF

OFF

OFF

OFF

OFF

OFF

0

1

ON

OFF

OFF

OFF

OFF

OFF

25

2

ON

ON

OFF

OFF

OFF

OFF

33

3

ON

OFF

ON

OFF

OFF

OFF

50

4

ON

ON

ON

OFF

OFF

OFF

58

5

ON

ON

ON

ON

OFF

OFF

67

6

ON

OFF

ON

OFF

ON

OFF

75

7

ON

OFF

ON

ON

ON

OFF

83

8

ON

ON

ON

ON

ON

OFF

92

9

ON

ON

ON

ON

ON

ON

100