Variable Air Volume Units Using Return Air
Sensor or Space Temperature Sensor —

To con-

figure the unit, perform the following:

1. The type of control is configured under Configuration

UNIT

C.TYP. Set C.TYP to 1 (VAV-RAT) for return

air sensor. Set C.TYP to 2 (VAV-SPT) for space tempera-

ture sensor.
NOTE: For VAV with a space sensor (VAV-SPT), under

Configuration

UNIT

SENS

SPT.S, enable the

space sensor by setting SPT.S to ENBL.

2. Install jumpers between R-W2 and W2-W1 on TB4 in

the control box.

3. The space temperature set points and the supply air set

points are configured under the Setpoints menu. The

heating and cooling set points must be configured. See

the Heating Control and Cooling Control sections for

further description on these configurations. Configure the

following set points:

4. To program time schedules, make sure SCH.N=1 under

Configuration

CCN

SC.OV

SCH.N to configure

the control to use local schedules.

5. Under the Timeclock

SCH.L submenu, enter the de-

sired schedule. See Time Clock Configuration section on

page 75 for further description of these configurations.

6. Under Configuration

SP

SP.SP, the supply duct Stat-

ic Pressure Setpoint should be configured.

7. If supply air temperature reset is desired, under the

Configuration

EDT.R submenu, the following set

points should be configured:

NOTE: Configure either RTIO and LIMT or RES.S. All three

are not used.

8. See the Economizer Options section on this page for ad-

ditional economizer option configurations.

9. See the Exhaust Options section on page 29 for additional

exhaust option configurations.

Multi-Stage Constant Volume Units with
Mechanical Thermostat —

To configure the unit, per-

form the following:

1. Under Configuration

UNIT

C.TYP, set C.TYP to 3

(TSTAT MULTI).

2. Remove jumpers from R-W2 and W2-W1 on TB4 in the

control box. Connect thermostat to TB4.

3. Under the Setpoints menu, set the following

configurations:

4. See the Economizer Options section on this page for ad-

ditional economizer option configurations.

5. See the Exhaust Options section on page 29 for additional

exhaust option configurations.

Multi-Stage Constant Volume Units with
Space Sensor —

To configure the unit, perform the

following:

1. Under Configuration

UNIT

C.TYP, set C.TYP to 5

(SPT MULTI).

2. Install jumpers between R-W2 and W2-W1 on TB4 in

the control box.

3. Under the Setpoints menu, the following configurations

should be set:

4. The degrees of demand from the space temperature set

points are configured under the Configuration

D.LV.T

submenu. See the Heating Control and Cooling Control

sections for further description on these configurations.

Configure the following set points:

5. Under Configuration

UNIT

SENS

SPT.S, enable

the space sensor by setting SPT.S to ENBL.

6. Under Configuration

UNIT

CV.FN, set CV.FN to 1

for continuous fan or 0 for automatic fan.

7. To program time schedules, set SCH.N=1 under Config-

uration

CCN

SC.OV

SCH.N to configure the con-

trol to use local schedules.

8. Under the Timeclock

SCH.L submenu, enter the de-

sired schedule. See Time Clock Configuration section on

page 75 for further description of these configurations.

9. See the Economizer Options section below for additional

economizer option configurations.

10. See the Exhaust Options section on page 29 for additional

exhaust option configurations.

Economizer Options —

Under the Configuration

ECON submenu, the following set points may be configured:

Configuration

ECON

EC.MN should always be set for

the minimum damper position.

OHSP

Occupied Heat Setpoint

OCSP

Occupied Cool Setpoint

UHSP

Unoccupied Heat Setpoint

V.C.ON VAV Occupied Cool On Delta
V.C.OF VAV Occupied Cool Off Delta
SASP

Supply Air Setpoint

SP.SP

Static Pressure Setpoint

RS.CF

EDT Reset Configuration

RTIO

Reset Ratio (if RS.CF = 1 or 2)

LIMT

Reset Limit (if RS.CF = 1 or 2)

RES.S

EDT 4-20 mA Reset Input (if RS.CF = 3)

SA.HI

Supply Air Set Point Hi

SA.LO

Supply Air Set Point Lo

OHSP

Occupied Heat Setpoint

OCSP

Occupied Cool Setpoint

UHSP

Unoccupied Heat Setpoint

UCSP

Unoccupied Cool Setpoint

GAP

Heat-Cool Setpoint Gap

SA.HI

Supply Air Set Point Hi

SA.LO

Supply Air Set Point Lo

L.H.ON Demand Level Lo Heat On
H.H.ON Demand Level Hi Heat On
L.H.OF Demand Level Lo Heat On
L.C.ON Demand Level Lo Cool On
H.C.ON Demand Level Hi Cool On
L.C.OF Demand Level Lo Cool On

EC.EN

Economizer Enabled?

EC.MN

Economizer Min.Position

EC.MX

Economizer Maximum Position

E.TRM

Economizer Trim for SumZ?

E.SEL

Econ Changeover Select

OA.E.C

OA Enthalpy Change Over Select

OA.EN

Outdoor Enthalpy Compare Value

OAT.L

High OAT Lockout Temp

O.DEW

OA Dew Point Temp Limit

ORH.S

Outside Air RH Sensor