Table 40B — Air Quantity Limits (50AJ,AK,AW,AY,A2,A3,A4,A5)

*Operation at these levels may be limited by entering evaporator air wet bulb temperatures.

CONTROLS QUICK START

The following section will provide a quick user guide to set-

ting up and configuring the A Series units with ComfortLink™

controls. See Basic Control Usage section on page 3 for infor-

mation on operating the control. For wiring information, refer

to unit wiring diagrams in the Major System Components sec-

tion on page 101.

Two-Stage Constant Volume Units with
Mechanical Thermostat —

To configure the unit, per-

form the following:

1. The type of control is configured under Configuration

UNIT

C.TYP. Set C.TYP to 4 (TSTAT 2 STG).

2. Remove jumpers from R-W2 and W2-W1 on TB4 in the

control box.

3. See Economizer Options section on page 28 for addition-

al economizer option configurations.

4. See Exhaust Options section on page 29 for additional

exhaust option configurations.

Two-Stage Constant Volume Units with Space
Sensor —

To configure the unit, perform the following:

1. The type of control is configured under Configuration

UNIT

C.TYP. Set C.TYP to 6 (SPT 2 STG).

2. Under Configuration

UNIT

SENS

SPT.S, enable

the space sensor by setting SPT.S to ENBL (enable).

3. Install jumpers between R-W2 and W2-W1 on TB4 in

the control box.

4. The space temperature set points are configured under the

Setpoints menu. The heating and cooling set points may

be configured. See the Heating Control and Cooling

Control sections on pages 50 and 37 for further descrip-

tion on these configurations. The following set points

may be configured:

5. The degrees of demand from the space temperature set

points are configured under the Configuration

D.LV.T

submenu. See the Heating Control and Cooling Control

sections for further description on these configurations.

The following set points may be configured:

6. Under Configuration

UNIT

CV.FN, set CV.FN to 1

for continuous fan or 0 for automatic fan.

7. To program time schedules, set SCH.N=1 under Config-

uration

CCN

SC.OV

SCH.N to configure the

control to use local schedules.

8. Under the Timeclock

SCH.L submenu, enter the

desired schedule. See Time Clock Configuration section

on page 75 for further description of these configurations.

9. Under the Configuration

CCN

SC.OV submenu, the

following schedules and overrides should be configured:

10. See Economizer Options section on page 28 for addition-

al economizer option configurations.

11. See Exhaust Options section on page 29 for additional

exhaust option configurations.

UNIT

COOLING

ELECTRIC HEAT

Min CFM

Max CFM*

Min CFM

Max CFM

50AJ,AW,A2,A3020

6,000

10,000

6,000

15,000

50AK,AY,A4,A5020

4,000

10,000

50AJ,AW,A2,A3025

7,500

12,500

50AK,AY,A4,A5025

5,000

12,500

50AJ,AW,A2,A4027

8,100

13,500

50AK,AY,A3,A5027

5,400

13,500

50AJ,AW,A2,A4030

9,000

15,000

50AK,AY,A3,A5030

6,000

15,000

50AJ,AW,A2,A4035

10,500

17,500

50AJ,AW036

10,500

17,500

50AK,AY,A3,A5035

7,000

17,500

50AK,AY036

7,000

17,500

50AJ,AW,A2,A4040

12,000

20,000

10,500

20,000

50AJ,AW041

12,000

20,000

50AK,AY,A3,A5040

8,000

20,000

50AK,AY041

8,000

20,000

50AJ,AW,A2,A4050

13,500

20,000

50AK,AY,A3,A5050

10,000

20,000

50AJ,AW051

18,000

27,000

15,000

27,000

50AJ,AW,A2,A4060

18,000

27,000

50AK,AY051

12,000

27,000

50AK,AY,A3,A5060

12,000

27,000

IMPORTANT: The ComfortLink controls provide the user

with numerous configuration options such as set points,

demand levels, reset, and many others. If the building

owner or design engineer has not provided specific recom-

mendations for these configuration settings, it is suggested

that the installer do not make changes to the default factory

settings. The factory-configured default values are appro-

priate for many applications.

IMPORTANT: The unit is shipped with the unit control

disabled. Enable the control by setting Local Machine Dis-

able (Service Test

STOP) to No.

OHSP

Occupied Heat Setpoint

OCSP

Occupied Cool Setpoint

UHSP

Unoccupied Heat Setpoint

UCSP

Unoccupied Cool Setpoint

GAP

Heat-Cool Setpoint Gap

L.H.ON

Demand Level Lo Heat On

H.H.ON

Demand Level Hi Heat On

L.H.OF

Demand Level Lo Heat Off

L.C.ON

Demand Level Lo Cool On

H.C.ON

Demand Level Hi Cool On

L.C.OF

Demand Level Lo Cool Off

O.T.L.

Override time limit

SPT.O

SPT override enabled?

T58.O

T58 override enabled?