Appendix e — upc open controller (cont), Local access to the upc open – Carrier WEATHERMAKER 48/50AJ User Manual
Page 174

174
APPENDIX E — UPC OPEN CONTROLLER (cont)
Table D — Open System Wiring Specifications and Recommended Vendors
LEGEND
Local access to the UPC Open —
The user can
use a BACview
6
handheld keypad display unit or the Virtual
BACview software as a local user interface to an Open control-
ler. These items let the user access the controller network infor-
mation. These are accessory items and do not come with the
UPC Open controller.
The BACview
6
unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will re-
quire an additional USB link cable for connection.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview
6
device.
To order a BACview
6
Handheld (BV6H), consult Commer-
cial Products i-Vu Open Control System Master Prices.
WIRING SPECIFICATIONS
RECOMMENDED VENDORS AND PART NUMBERS
Wire Type
Description
Connect Air
International
Belden
RMCORP
Contractors
Wire and Cable
MS/TP
Network (RS-485)
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
W221P-22227
—
25160PV
CLP0520LC
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
W241P-2000F
82841
25120-OR
—
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
W184C-2099BLB
6302UE
21450
CLP0442
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
Fig. F — BACview
6
Device Connection
a48-8583