Fig. 4 — mode selection – Carrier WEATHERMAKER 48/50AJ User Manual

Page 34

background image

34

System Mode =

OFF?

Inputs -> FIRE ->

FSD in alarm?

HVAC Mode = OFF

(Fire Shutdown)

HVAC Mode = OFF

(Disabled)

Unit not in factory

test AND fire-smoke

control mode is

alarming?

Inputs -> FIRE ->

PRES in alarm?

HVAC Mode = OFF

(Pressurization)

Inputs -> FIRE ->

EVAC in alarm?

HVAC Mode = OFF

(Evacuation)

HVAC Mode = OFF

(Purge)

Config->UNIT->
C.TYP changed

while unit running?

15-second delay

HVAC Mode = OFF

(Disabled)

System Mode =

TEST?

HVAC Mode = TEST

Service Test ->

S.STP = YES?

HVAC Mode = SoftStop

Request

Config->UNIT->
RM.CF =2 AND

Inputs->GEN.I->

REMT = ON

HVAC Mode = OFF
(Rem. Sw. Disable)

Config->SP-> SP.CF

= 1 OR 2

HVAC Mode = OFF

(Static Pres. Fail)

Config->UNIT->

SFS.M=1 OR 2 AND

Config->UNIT->

SFS.S=YES?

HVAC Mode = OFF

(Fan Status Fail)

HVAC Mode = OFF

(Starting Up)

Unit shutting down?

HVAC Mode = Shutting

Down

Unit control free to select

normal heating/cooling

HVAC mode

HVAC Mode = OFF

HVAC Mode =

Tempering Vent

HVAC Mode =

Tempering LoCool

HVAC Mode =

Tempering HiCool

HVAC Mode = Vent

HVAC Mode = Low Cool

HVAC Mode = High Cool

HVAC Mode = Low Heat

HVAC Mode = High Heat

HVAC Mode = Unocc.

Free Cool

No

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

System

Mode

Fire-

Smoke

Control

Exceptions

Unit

control free

to choose

HVAC

Mode

and static pressure

sensor has failed

and supply fan

has failed

Yes

Yes

Yes

Yes

No

No

No

No

Unit just waking up

from power reset?

HVAC Mode =

Compressor Stuck On

Fig. 4 — Mode Selection