Table 52 — Staging Sequence with Hot Gas Bypass —

48/50AK,AY020-027 and Multi-Stage 48/50AJ,AW020-027

*With Minimum Load Valve ON.

Table 53 — Staging Sequence without Hot Gas Bypass —

48/50AK,AY030-060 and Multi-Stage 48/50AJ,AW030-060

Table 54 — Staging Sequence with Hot Gas Bypass — 48/50AK,AY030-060

*With minimum load valve ON.

Table 55 — 2-Stage Sequence —

48/50A2,A4020-027

Table 56 — 2-Stage Sequence —

48/50A2,A4030-060

STAGE

SEQUENCE 1

SEQUENCE 2

0

1

2

3

4

5

0

1

2

3

4

5

COMP

Compressor Status

Compressor Status

A1

OFF

ON*

ON

ON

OFF

ON

OFF

OFF

OFF

ON

ON

ON

A2

OFF

OFF

OFF

ON

ON

ON

OFF

ON*

ON

ON

OFF

ON

B1

OFF

OFF

OFF

OFF

ON

ON

OFF

OFF

OFF

OFF

ON

ON

UNIT

Unit Capacity 48/50A

Unit Capacity 48/50A

020

0%

18%

33%

67%

67%

100%

0%

18%

33%

67%

67%

100%

025

0%

17%

30%

65%

70%

100%

0%

22%

35%

65%

65%

100%

027

0%

21%

33%

67%

67%

100%

0%

21%

33%

67%

67%

100%

STAGE

SEQUENCE 1

SEQUENCE 2

0

1

2

3

4

5

0

1

2

3

4

5

COMP

Compressor Status

Compressor Status

A1

OFF

ON

ON

OFF

ON

ON

OFF

OFF

ON

ON

ON

ON

A2

OFF

OFF

ON

ON

ON

ON

OFF

ON

ON

OFF

ON

ON

B1

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

ON

B2

OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

ON

ON

ON

UNIT

Unit Capacity 48/50A

Unit Capacity 48/50A

030

0%

23%

45%

50%

73%

100%

0%

23%

45%

50%

73%

100%

035,036

0%

22%

48%

52%

74%

100%

0%

26%

48%

48%

74%

100%

040,041

0%

21%

43%

50%

71%

100%

0%

21%

43%

50%

72%

100%

050

0%

23%

46%

46%

68%

100%

0%

23%

46%

54%

77%

100%

051

0%

25%

50%

50%

75%

100%

0%

25%

50%

50%

75%

100%

060

0%

24%

50%

50%

74%

100%

0%

26%

50%

50%

76%

100%

STAGE

SEQUENCE 1

SEQUENCE 2

0

1

2

3

4

5

6

0

1

2

3

4

5

6

COMP

Compressor Status

Compressor Status

A1

OFF

ON*

ON

ON

OFF

ON

ON

OFF

OFF

OFF

ON

ON

ON

ON

A2

OFF

OFF

OFF

ON

ON

ON

ON

OFF

ON*

ON

ON

OFF

ON

ON

B1

OFF

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

ON

B2

OFF

OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

ON

OFF

ON

ON

ON

UNIT

Unit Capacity 48/50A

Unit Capacity 48/50A

030

0%

12%

23%

45%

50%

73%

100%

0%

12%

23%

45%

50%

73%

100%

035,036

0%

12%

22%

48%

52%

74%

100%

0%

16%

26%

48%

48%

74%

100%

040,041

0%

13%

21%

43%

50%

71%

100%

0%

13%

21%

43%

50%

72%

100%

050

0%

16%

23%

46%

46%

68%

100%

0%

16%

23%

46%

54%

77%

100%

051

0%

19%

25%

50%

50%

75%

100%

0%

19%

25%

50%

50%

75%

100%

060

0%

19%

24%

50%

50%

74%

100%

0%

21%

26%

50%

50%

76%

100%

STAGE

SEQUENCE 1

SEQUENCE 2

0

1

2

0

1

2

Thermostat Inputs

Thermostat Inputs

Y1

OPEN CLOSED CLOSED OPEN CLOSED CLOSED

Y2

OPEN

OPEN

CLOSED OPEN

OPEN

CLOSED

COMP

Compressor Status

Compressor Status

A1

OFF

ON

ON

OFF

OFF

ON

A2

OFF

OFF

ON

OFF

ON

ON

B1

OFF

OFF

ON

OFF

OFF

ON

UNIT

Unit Capacity

Unit Capacity

020

0%

30%

100%

0%

30%

100%

025

0%

33%

100%

0%

33%

100%

027

0%

33%

100%

0%

33%

100%

STAGE

SEQUENCE 1

SEQUENCE 2

0

1

2

0

1

2

Thermostat Inputs

Thermostat Inputs

Y1

OPEN CLOSED CLOSED OPEN CLOSED CLOSED

Y2

OPEN

OPEN

CLOSED OPEN

OPEN

CLOSED

COMP

Compressor Status

Compressor Status

A1

OFF

ON

ON

OFF

OFF

ON

A2

OFF

OFF

ON

OFF

ON

ON

B1

OFF

ON

ON

OFF

OFF

ON

B2

OFF

OFF

ON

OFF

ON

ON

UNIT

Unit Capacity

Unit Capacity

030

0%

50%

100%

0%

50%

100%

035

0%

50%

100%

0%

50%

100%

040

0%

50%

100%

0%

50%

100%

050

0%

50%

100%

0%

50%

100%

060

0%

50%

100%

0%

50%

100%