APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
LEGEND
BACNET
OBJECT ID
POINT NAME
READ
ONLY
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
UNIT
POINT
BV:1052
Filter Status Input
W
n/a
n/a
0-1
filter_status_1
FLTS
BV:1060
Evacuation Input
W
n/a
n/a
0-1
smk_evac_1
EVAC
BV:1061
Pressurization Input
W
n/a
n/a
0-1
smk_press_1
PRES
BV:1062
Smoke Purge Input
W
n/a
n/a
0-1
smk_purg_1
PURG
BV:2001
Supply Fan State
R
n/a
n/a
n/a
sfan_1
SFAN
BV:2004
Supply Fan Request
W
n/a
n/a
0-1
sfan_forc_1
SFANFORC
BV:2008
Occupied?
W
n/a
n/a
0-1
occ_status_1
OCCUPIED
BV:2012
Condenser Fan Circuit A
R
n/a
n/a
n/a
cond_fan_a_1
CONDFANA
BV:2013
Condenser Fan Circuit B
R
n/a
n/a
n/a
cond_fan_b_1
CONDFANB
BV:2014
Remote Alarm/Aux Relay
W
n/a
n/a
0-1
aux_relay_1
ALRM
BV:2911
User Defined Binary 1
n/a
n/a
n/a
n/a
user_binary_1_1
n/a
BV:2912
User Defined Binary 2
n/a
n/a
n/a
n/a
user_binary_2_1
n/a
BV:2913
User Defined Binary 3
n/a
n/a
n/a
n/a
user_binary_3_1
n/a
BV:2914
User Defined Binary 4
n/a
n/a
n/a
n/a
user_binary_4_1
n/a
BV:2915
User Defined Binary 5
n/a
n/a
n/a
n/a
user_binary_5_1
n/a
BV:2999
Element Comm Status
n/a
n/a
n/a
n/a
element_stat_1
n/a
BP
— Building Pressure
CEM
— Controls Expansion Module
DAQ
— Differential Air Quality
DBC
— Dry Bulb Changeover
DDBC
— Differential Dry Bulb Changeover
DEC
— Differential Enthalpy Changeover
DH
— Dehumidification
IAQ
— Indoor Air Quality
LAT
— Leaving Air Temperature
n/a
— Not Available
OAEC
— Outdoor Air Enthalpy Changeover
OAT
— Outdoor Air Temperature
PID
— Proportional, Integral, Derivative
R
— Read
RAT
— Return Air Temperature
RH
— Relative Humidity
SASP
— Supply Air Set Point
SPT
— Space Temperature
TSTAT
— Thermostat
VAV
— Variable Air Volume
VFD
— Variable Frequency Drive
W
— Write