APPENDIX E — UPC OPEN CONTROLLER (cont)

NETWORK POINTS LIST (cont)

See legend on page 182.

BACNET

OBJECT ID

POINT NAME

READ

ONLY

UNITS

DEFAULT

VALUE

RANGE

BACNET

OBJECT NAME

UNIT

POINT

BV:59

Local Machine Disable

W

n/a

No

0-1

unitstop_1

UNITSTOP

BV:60

Low BP Override

R

n/a

n/a

n/a

bplpovrd_1

BPLPOVRD

BV:61

Low Temp Cap Override

R

n/a

n/a

n/a

low_temp_1

LOW_TEMP

BV:63

Mech Cooling Locked Out

R

n/a

n/a

n/a

modelock_1

MODELOCK

BV:64

Min. Load Valve (HGBP)

R

n/a

n/a

n/a

mlv_1

MLV

BV:67

OAEC- OA Enth Lockout?

R

n/a

n/a

n/a

oaecstat_1

OAECSTAT

BV:68

OAQ Lockout In Effect ?

R

n/a

n/a

n/a

oaqlockd_1

OAQLOCKD

BV:69

OAT Sensor Bad ?

R

n/a

n/a

n/a

oat_stat_1

OAT_STAT

BV:70

Occupied Heating Enabled

W

n/a

No

0-1

htoccena_1

HTOCCENA

BV:72

Power Exhaust Relay A

R

n/a

n/a

n/a

pe_a_1

PE_A

BV:73

Power Exhaust Relay B

R

n/a

n/a

n/a

pe_b_1

PE_B

BV:74

Power Exhaust Relay C

R

n/a

n/a

n/a

pe_c_1

PE_C

BV:75

Pull Down Cap Override

R

n/a

n/a

n/a

pulldown_1

PULLDOWN

BV:76

Relay 3 W1 Gas Valve 2

R

n/a

n/a

n/a

hs3_1

HS3

BV:77

Relay 4 W2 Gas Valve 2

R

n/a

n/a

n/a

hs4_1

HS4

BV:78

Relay 5 W1 Gas Valve 3

R

n/a

n/a

n/a

hs5_1

HS5

BV:79

Relay 6 W2 Gas Valve 3

R

n/a

n/a

n/a

hs6_1

HS6

BV:80

Remote Econ. Disabled ?

R

n/a

n/a

n/a

econdisa_1

ECONDISA

BV:81

Remote Input State

W

n/a

n/a

0-1

rmtin_1

RMTIN

BV:86

Slow Change Cap Override

R

n/a

n/a

n/a

slo_chng_1

SLO_CHNG

BV:87

Soft Stop Request

W

n/a

n/a

0-1

softstop_1

SOFTSTOP

BV:93

Supply Air Reset

R

n/a

n/a

n/a

modesars_1

MODESARS

BV:94

Supply Fan Relay

R

n/a

n/a

n/a

sfan_rly_1

SFAN_RLY

BV:95

Supply Fan Status Switch

W

n/a

n/a

0-1

sfs_1

SFS

BV:96

Temp Compensated Start

R

n/a

n/a

n/a

modetcst_1

MODETCST

BV:97

Timed Override In Effect

R

n/a

n/a

n/a

modetovr_1

MODETOVR

BV:98

Timed-Override in Effect

R

n/a

n/a

n/a

overlast_1

OVERLAST

BV:99

TSTAT Both Heat and Cool

W

n/a

No

0-1

tstatall_1

TSTATALL

BV:1005

Fire Shutdown Input

W

n/a

n/a

0-1

firedown_status_1

FSD

BV:1006

Demand Limit Switch 1

W

n/a

n/a

0-1

dmd_sw1_1

DMD_SW1

BV:1007

Demand Limit Switch 2

W

n/a

n/a

0-1

dmd_sw2_1

DMD_SW2

BV:1010

Remote Economizer Enable

W

n/a

n/a

0-1

remote_econ_enable_1

ECONENBL

BV:1017

Thermostat Y1 Input

W

n/a

n/a

0-1

y1_input_1

Y1

BV:1018

Thermostat Y2 Input

W

n/a

n/a

0-1

y2_input_1

Y2

BV:1019

Thermostat W1 Input

W

n/a

n/a

0-1

w1_input_1

W1

BV:1020

Thermostat W2 Input

W

n/a

n/a

0-1

w2_input_1

W2

BV:1021

Thermostat G Input

W

n/a

n/a

0-1

g_input_1

G

BV:1026

Heat Interlock Relay

W

n/a

n/a

0-1

heat_interlock_relay_1

HIR

BV:1050

IAQ - Discrete Input

W

n/a

n/a

0-1

iaq_status_1

IAQIN