APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
See legend on page 182.
BACNET
OBJECT ID
POINT NAME
READ
ONLY
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
UNIT
POINT
BV:59
Local Machine Disable
W
n/a
No
0-1
unitstop_1
UNITSTOP
BV:60
Low BP Override
R
n/a
n/a
n/a
bplpovrd_1
BPLPOVRD
BV:61
Low Temp Cap Override
R
n/a
n/a
n/a
low_temp_1
LOW_TEMP
BV:63
Mech Cooling Locked Out
R
n/a
n/a
n/a
modelock_1
MODELOCK
BV:64
Min. Load Valve (HGBP)
R
n/a
n/a
n/a
mlv_1
MLV
BV:67
OAEC- OA Enth Lockout?
R
n/a
n/a
n/a
oaecstat_1
OAECSTAT
BV:68
OAQ Lockout In Effect ?
R
n/a
n/a
n/a
oaqlockd_1
OAQLOCKD
BV:69
OAT Sensor Bad ?
R
n/a
n/a
n/a
oat_stat_1
OAT_STAT
BV:70
Occupied Heating Enabled
W
n/a
No
0-1
htoccena_1
HTOCCENA
BV:72
Power Exhaust Relay A
R
n/a
n/a
n/a
pe_a_1
PE_A
BV:73
Power Exhaust Relay B
R
n/a
n/a
n/a
pe_b_1
PE_B
BV:74
Power Exhaust Relay C
R
n/a
n/a
n/a
pe_c_1
PE_C
BV:75
Pull Down Cap Override
R
n/a
n/a
n/a
pulldown_1
PULLDOWN
BV:76
Relay 3 W1 Gas Valve 2
R
n/a
n/a
n/a
hs3_1
HS3
BV:77
Relay 4 W2 Gas Valve 2
R
n/a
n/a
n/a
hs4_1
HS4
BV:78
Relay 5 W1 Gas Valve 3
R
n/a
n/a
n/a
hs5_1
HS5
BV:79
Relay 6 W2 Gas Valve 3
R
n/a
n/a
n/a
hs6_1
HS6
BV:80
Remote Econ. Disabled ?
R
n/a
n/a
n/a
econdisa_1
ECONDISA
BV:81
Remote Input State
W
n/a
n/a
0-1
rmtin_1
RMTIN
BV:86
Slow Change Cap Override
R
n/a
n/a
n/a
slo_chng_1
SLO_CHNG
BV:87
Soft Stop Request
W
n/a
n/a
0-1
softstop_1
SOFTSTOP
BV:93
Supply Air Reset
R
n/a
n/a
n/a
modesars_1
MODESARS
BV:94
Supply Fan Relay
R
n/a
n/a
n/a
sfan_rly_1
SFAN_RLY
BV:95
Supply Fan Status Switch
W
n/a
n/a
0-1
sfs_1
SFS
BV:96
Temp Compensated Start
R
n/a
n/a
n/a
modetcst_1
MODETCST
BV:97
Timed Override In Effect
R
n/a
n/a
n/a
modetovr_1
MODETOVR
BV:98
Timed-Override in Effect
R
n/a
n/a
n/a
overlast_1
OVERLAST
BV:99
TSTAT Both Heat and Cool
W
n/a
No
0-1
tstatall_1
TSTATALL
BV:1005
Fire Shutdown Input
W
n/a
n/a
0-1
firedown_status_1
FSD
BV:1006
Demand Limit Switch 1
W
n/a
n/a
0-1
dmd_sw1_1
DMD_SW1
BV:1007
Demand Limit Switch 2
W
n/a
n/a
0-1
dmd_sw2_1
DMD_SW2
BV:1010
Remote Economizer Enable
W
n/a
n/a
0-1
remote_econ_enable_1
ECONENBL
BV:1017
Thermostat Y1 Input
W
n/a
n/a
0-1
y1_input_1
Y1
BV:1018
Thermostat Y2 Input
W
n/a
n/a
0-1
y2_input_1
Y2
BV:1019
Thermostat W1 Input
W
n/a
n/a
0-1
w1_input_1
W1
BV:1020
Thermostat W2 Input
W
n/a
n/a
0-1
w2_input_1
W2
BV:1021
Thermostat G Input
W
n/a
n/a
0-1
g_input_1
G
BV:1026
Heat Interlock Relay
W
n/a
n/a
0-1
heat_interlock_relay_1
HIR
BV:1050
IAQ - Discrete Input
W
n/a
n/a
0-1
iaq_status_1
IAQIN