beautypg.com

Carrier 48AJ User Manual

Installation, start-up and service instructions

background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 534-739

Printed in U.S.A.

Form 48A,E-1SI

Pg 1

107 11-01

Replaces: 48E-6SI

Book 1

Tab

1a

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-58

Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . . . 1

• ROOF CURB

• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit

. . . . . . . . . . . . . . . . . . . . . 2

• POSITIONING

• ROOF MOUNT
Step 3 — Field Fabricate Ductwork

. . . . . . . . . . . . . . . 2

Step 4 — Make Unit Duct Connections

. . . . . . . . . . . 2

Step 5 — Install Flue Hood

. . . . . . . . . . . . . . . . . . . . . . 28

Step 6 — Trap Condensate Drain

. . . . . . . . . . . . . . . . 28

Step 7 — Install Gas Piping

. . . . . . . . . . . . . . . . . . . . . 28

Step 8 — Controls Options

. . . . . . . . . . . . . . . . . . . . . . 29

• STAGED GAS UNIT APPLICATIONS

• THERMISTORS

• CONSTANT VOLUME APPLICATIONS

• VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 9 — Make Electrical Connections

. . . . . . . . . . 33

• POWER WIRING

• FIELD POWER SUPPLY

• FIELD CONTROL WIRING
Step 10 — Make Outdoor-Air Inlet

Adjustments

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

• ECONOMIZER

• ECONOMIZER SETTINGS
Step 11 — Position Power Exhaust/Barometric

Relief Damper Hood

. . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Step 12 — Install All Accessories

. . . . . . . . . . . . . . . 54

Step 13 — Field Modifications

. . . . . . . . . . . . . . . . . . . 57

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-89

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89-102

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . 103-115

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . CL-1,CL-2

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo-

nents. Only trained and qualified service personnel should in-

stall, repair, or service air-conditioning equipment.

Untrained personnel can perform the basic maintenance

functions of cleaning coils and filters and replacing filters. All

other operations should be performed by trained service per-

sonnel. When working on air-conditioning equipment, observe

precautions in the literature, tags and labels attached to the unit,

and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have

fire extinguishers available for all brazing operations.

INSTALLATION

Step 1 — Provide Unit Support

Before performing service or maintenance operations on

unit, turn off main power switch to unit. Electrical shock

could cause personal injury.

1. Improper installation, adjustment, alteration, service,

or maintenance can cause property damage, personal

injury, or loss of life. Refer to the User’s Information

Manual provided with this unit for more details.

2. Do not store or use gasoline or other flammable va-

pors and liquids in the vicinity of this or any other

appliance.

What to do if you smell gas:

1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any

phone in your building.

3. IMMEDIATELY call your gas supplier from a neigh-

bor’s phone. Follow the gas supplier’s instructions.

4. If you cannot reach your gas supplier, call the fire

department.

Disconnect gas piping from unit when pressure testing at

pressure greater than 0.5 psig. Pressures greater than

0.5 psig will cause gas valve damage resulting in hazardous

condition. If gas valve is subjected to pressure greater than

0.5 psig, it must be replaced before use. When pressure

testing field-supplied gas piping at pressures of 0.5 psig or

less, a unit connected to such piping must be isolated by

closing the manual gas valve(s).

1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.

48AJ,AK,AW,AY020-060

with Reciprocating Compressor

48EJ,EK,EW,EY024-068

Single Package Rooftop Units

Electric Cooling/Gas Heating

This manual is related to the following products: