beautypg.com

Carrier WEATHERMAKER 48/50AJ User Manual

Page 170

background image

170

APPENDIX D — MODE SELECTION PROCESS

The following section is to be used in conjunction with

Fig. 4 on page 34. To help determine why the unit controls are

in a certain mode, the programming logic is provided below.

The software will proceed, step by step, until a mode is

reached. If an “If” statement is true, then that mode will be en-

tered. The “Else” statement refers to other possible choices.

If the System Mode is OFF:
{ If the fire shut down input (Inputs

FIRE

FSD)

is in “alarm”:

HVAC mode:

("Fire Shut Down ") OFF

Else

HVAC mode:

("Disabled ") OFF}

Else If: The rooftop is not in “factory test” and a fire

smoke-control mode is “alarming”:

{ If the pressurization input (Inputs

FIRE

PRES)

is in “alarm”:

HVAC mode:

("Pressurization ")

Else If the evacuation input (Inputs

FIRE

EVAC)

is in “alarm”:

HVAC mode:

("Evacuation ")

Else If the smoke purge input (Inputs

FIRE

PURG)

is in “alarm”:

HVAC mode:

("Smoke Purge ")}

Else If: Someone changed the machine’s

control type (Configuration

UNIT

C.TYP) during

run time, a 15 second delay is called out:

{

HVAC mode:

("Disabled ") OFF}

Else If: The System Mode is TEST:

{

HVAC mode:

("Test ")}

Else If: The “soft stop” command (Service Test

S.STP)

is forced to YES:

{

HVAC mode:

("SoftStop Request")}

Else If: The remote switch config (Configuration

UNIT

RM.CF)=2; “start/stop”, and the remote

input state (Inputs

GEN.I

REMT)=ON:

{

HVAC mode:

("Rem. Sw. Disable") OFF}

Else If: Configured for static pressure control

(Configuration

SP

SP.CF = 1,2) and the static

pressure sensor (Pressures

AIR.P

SP) fails:

{

HVAC mode:

("Static Pres.Fail") OFF}

Else If: Configured for supply fan status monitoring

(Configuration

UNIT

SFS.M = 1,2) and

configured to shut the unit down on fan status fail

(Configuration

UNIT

SFS.S = YES)

{

HVAC mode:

("Fan Status Fail ") OFF}

Else If: The unit is just waking up from a power reset

{

HVAC mode:

("Starting Up ") OFF}

Else If: A compressor is diagnosed as being “Stuck On”

{

HVAC mode:

("Comp. Stuck On ")

Else The control is free to select the normal heating/

cooling HVAC modes:

{

HVAC mode:

("Off ")

— The unit is off and no operating modes are active.

HVAC mode:

("Tempering Vent ")

— The economizer is at minimum vent position but

the supply air temperature has dropped below the

tempering vent set point. Gas heat is used to

temper the ventilation air.
HVAC mode:

("Tempering LoCool")

— The economizer is at minimum vent position but

the combination of the outside-air temperature and

the economizer position has dropped the supply-air

temperature below the tempering cool set point.

Gas heat is used to temper the ventilation air.
HVAC mode:

("Tempering HiCool")

— The economizer is at minimum vent position but

the combination of the outside air temperature and

the economizer position has dropped the supply air

temperature below the tempering cool set point.

Gas heat is used to temper the ventilation air.
HVAC mode:

(“Re-Heat”)

The unit is operating in reheat mode.
HVAC mode:

(“Dehumidification”)

The unit is operating in dehumidification mode.
HVAC mode:

("Vent ")

This is a normal operation mode where no heating

or cooling is required and outside air is being

delivered to the space to control IAQ levels.
HVAC mode:

("Low Cool ")

This is a normal cooling mode when a low cooling

demand exists.
HVAC mode:

("High Cool ")

This is a normal cooling mode when a high

cooling demand exists.
HVAC mode:

("Low Heat ")

This is a normal heating mode when a low

heating demand exists.
HVAC mode:

("High Heat ")

This is a normal heating mode when a high

heating demand exists.
HVAC mode:

("Unocc. Free Cool")

In this mode the unit will operate in cooling but

will be using the economizer for free cooling.

Entering this mode will depend on the status of the

outside air. The unit can be configured for outside

air changeover, differential dry bulb changeover,

outside air enthalpy changeover, differential

enthalpy changeover, or a custom arrangement

of enthalpy/dewpoint and dry bulb. See the

Economizer section for further details.}

NOTE: There is also a transitional mode whereby the machine

may be waiting for relay timeguards to expire before shutting

the machine completely down:

HVAC mode:

("Shutting Down ")