beautypg.com

Appendix b — ccn tables (cont) – Carrier WEATHERMAKER 48/50AJ User Manual

Page 156

background image

156

APPENDIX B — CCN TABLES (cont)

MAINTENANCE DISPLAY TABLES

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

ALARMS01

Active Alarm

ascii

ALARM_01

------------------------

ascii

Active Alarm

ascii

ALARM_02

------------------------

ascii

Active Alarm

ascii

ALARM_03

------------------------

ascii

Active Alarm

ascii

ALARM_04

------------------------

ascii

follow same format for…
ALARMS02
ALARMS03
ALARMS04
ALARMS05
COMPRESR

Compressor A1 Relay

On/Off

CMPA1

Compressor A1 Feedback

On/Off

CSB_A1

Curr.Sens.Brd. A1 Status

ascii

CSBA1ASC

CSB A1 Feedback Alarm

Enable/Disable

CSB_A1EN

config

Comp A1 Locked Out ?

Yes/No

CMPA1LOK

Compressor A1 Strikes

CMPA1STR

Enable Compressor A1

Enable/Disable

CMPA1ENA

config

Compressor A2 Relay

On/Off

CMPA2

Compressor A2 Feedback

On/Off

CSB_A2

Curr.Sens.Brd. A2 Status

ascii

CSBA2ASC

CSB A2 Feedback Alarm

Enable/Disable

CSB_A2EN

config

Comp A2 Locked Out ?

Yes/No

CMPA2LOK

Compressor A2 Strikes

CMPA2STR

Enable Compressor A2

Enable/Disable

CMPA2ENA

config

Compressor B1 Relay

On/Off

CMPB1

Compressor B1 Feedback

On/Off

CSB_B1

Curr.Sens.Brd. B1 Status

ascii

CSBB1ASC

CSB B1 Feedback Alarm

Enable/Disable

CSB_B1EN

config

Comp B1 Locked Out ?

Yes/No

CMPB1LOK

Compressor B1 Strikes

CMPB1STR

Enable Compressor B1

Enable/Disable

CMPB1ENA

config

Compressor B2 Relay

On/Off

CMPB2

Compressor B2 Feedback

On/Off

CSB_B2

Curr.Sens.Brd. B2 Status

ascii

CSBB2ASC

CSB B2 Feedback Alarm

Enable/Disable

CSB_B2EN

config

Comp B2 Locked Out ?

Yes/No

CMPB2LOK

Compressor B2 Strikes

CMPB2STR

Enable Compressor B2

Enable/Disable

CMPB2ENA

config

DMANDLIM

Active Demand Limit

0-100

%

DEM_LIM

forcible

Percent Total Capacity

0-100

%

CAPTOTAL

Demand Limit Select

0-3

DMD_CTRL

config

Demand Limit Switch 1

On/Off

DMD_SW1

forcible

Demand Limit Switch 2

On/Off

DMD_SW2

forcible

Demand Limit Sw.1 Setpt.

0-100

%

DLSWSP1

config

Demand Limit Sw.2 Setpt.

0-100

%

DLSWSP2

config

4-20 ma Demand Signal

4-20

ma

DMDLMTMA

forcible

Demand Limit at 20 ma

0-100

%

DMT20MA

config

CCN Loadshed Signal

0-99

DL_STAT

Loadshed Group Number

0-99

SHED_NUM

config

Loadshed Demand Delta

0-60

%

SHED_DEL

config

Maximum Loadshed Time

0-120

min

SHED_TIM

config