Appendix b — ccn tables (cont) – Carrier WEATHERMAKER 48/50AJ User Manual
Page 160

160
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TIME SCHEDULE CONFIG TABLE
Allowable Entries: Day not selected = 0 Day selected = 1
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
TESTCOOL
Compressor A1 Relay
ON/OFF
CMPA1TST
test
Compressor A2 Relay
ON/OFF
CMPA2TST
test
Min. Load Valve (HGBP)
ON/OFF
MLV_TST
test
Compressor B1 Relay
ON/OFF
CMPB1TST
test
Compressor B2 Relay
ON/OFF
CMPB2TST
test
TESTFANS
Supply Fan Relay
ON/OFF
SFAN_TST
test
Supply Fan VFD Speed
0-100
%
SGVFDTST
test
Condenser Fan Circuit A
ON/OFF
CNDA_TST
test
Condenser Fan Circuit B
ON/OFF
CNDB_TST
test
TESTHEAT
Requested Heat Stage
0-MAX
HTST_TST
test
Heat Relay 1
ON/OFF
HS1_TST
test
Heat Relay 2
ON/OFF
HS2_TST
test
Relay 3 W1 Gas Valve 2
ON/OFF
HS3_TST
test
Relay 4 W2 Gas Valve 2
ON/OFF
HS4_TST
test
Relay 5 W1 Gas Valve 3
ON/OFF
HS5_TST
test
Relay 6 W2 Gas Valve 3
ON/OFF
HS6_TST
test
TESTINDP
Economizer Position Test
ECONCTST
test
Economizer Power Test
ECONPTST
test
Calibrate the Economizer?
ECON_CAL
test
Power Exhaust Relay A
PE_A_TST
test
Power Exhaust Relay B
PE_B_TST
test
Power Exhaust Relay C
PE_C_TST
test
Heat Interlock Relay
ON/OFF
HIR_TST
test
Remote Alarm/Aux Relay
ON/OFF
ALRM_TST
test
VERSIONS
MBB CESR131343-
ascii version#
MBB_SW
ECB1 CESR131249-
ascii version#
ECB1_SW
ECB2 CESR131249-
ascii version#
ECB2_SW
SCB CESR131226-
ascii version#
SCB_SW
CEM CESR131174-
ascii version#
CEM_SW
MARQUEE CESR131171-
ascii version#
MARQ_SW
NAVIGATOR CESR130227-
ascii version#
NAVI_SW
DAY FLAGS
MTWTFSSH
OCCUPIED
TIME
UNOCCUPIED
TIME
Period 1:
00000000
00:00
00:00
Period 2:
00000000
00:00
00:00
Period 3:
00000000
00:00
00:00
Period 4:
00000000
00:00
00:00
Period 5:
00000000
00:00
00:00
Period 6:
00000000
00:00
00:00
Period 7:
00000000
00:00
00:00
Period 8:
00000000
00:00
00:00