beautypg.com

Carrier WEATHERMAKER 48/50AJ User Manual

Page 31

background image

31

THIRD PARTY CONTROL

Thermostat —

The method of control would be through

the thermostat inputs:

Y1 = first stage cooling

Y1 and Y2 = first and second stage cooling

W1 = first stage heating

W1 and W2 = first and second stage heating

G = supply fan

Alarm Output —

The alarm output TB4-7 and 8, will pro-

vide relay closure whenever the unit is under an alert or alarm

condition.

Remote Switch —

The remote switch may be configured

for three different functions. Under Configuration

UNIT, set

RM.CF to one of the following:

0 = no remote switch

1 = occupied/unoccupied switch

2 = start/stop switch

3 = occupancy override switch
With RM.CF set to 1, no time schedules are followed and

the unit follows the remote switch only in determining the state

of occupancy.

With RM.CF set to 2, the remote switch can be used to shut

down and disable the unit, while still honoring time guards on

compressors. Time schedules, internal or external, may be run

simultaneously with this configuration.

With RM.CF set to 3, the remote input may override an

unoccupied state and force the control to go into occupied

mode. As with the start/stop configuration, an internal or exter-

nal time schedule may continue to control occupancy when the

switch is not in effect.

Under Configuration

SW.LG

RMI.L, the remote occu-

pancy switch can be set to either a normally open or normally

closed switch input. Normal is defined as either unoccupied, start

or “not currently overridden,” respective to the RM.CF

configuration.

VFD Control —

On VFD equipped supply fans, supply

duct static pressure control may be left under unit control or be

externally controlled. To control a VFD externally with a 4 to

20 mA signal, set SP.RS to 4, under the Configuration

SP

menu. This will set the reset to VFD control. When SP.RS = 4,

the static pressure reset function acts to provide direct VFD

speed control where 4 mA = 0% speed and 20 mA = 100%

(SP.MN and SP.MX will override). Note that SP.CF must be

set to 1 (VFD Control) prior to configuring SP.RS = 4. Failure

to do so could result in damage to ductwork due to overpressur-

ization. In effect, this represents a speed control signal “pass

through” under normal operating circumstances. The Com-

fortLink controller overrides the third party signal for critical

operation situations, most notably smoke and fire control. Wire

the input to the controls expansion module (CEM) using TB-11

and 12. An optional CEM board is required.

See Appendix C and the VFD literature supplied with the unit

for VFD configurations and field wiring connections to the VFD.

Supply Air Reset —

With the installation of the CEM,

the ComfortLink controller is capable of accepting a 4 to

20 mA signal, to reset the supply-air temperature up to a maxi-

mum of 20 F. See VFD Control section above.

Demand Limit Control —

The term “demand limit

control” refers to the restriction of the machine’s mechanical

cooling capacity to control the amount of power that a machine

may use.
Demand limiting using mechanical control is possible via two

means:
Two discrete inputs tied to demand limit set point percentages.
OR

A 4 to 20 mA input that can reduce or limit

capacity linearly to

a set point percentage.

In either case, it will be necessary to install a controls ex-

pansion module (CEM).
DEMAND LIMIT DISCRETE INPUTS — First, set DM.L.S

in Configuration

DMD.L to 1 (2 switches).

When Inputs

GEN.I

DL.S1 (Demand Switch no. 1) is

OFF, the control will not set any limit to the capacity, and

when ON, the control sets a capacity limit to the Configura-

tion

DMD.L

D.L.S1 set point.

Likewise, when Inputs

GEN.I

DL.S2 (Demand Switch

no. 2) is OFF, the control will not set any limit to the capacity,

and when ON, the control sets a capacity limit to the Configu-

ration

DMD.L

D.L.S2 set point.

If both switches are ON, Inputs

GEN.I

DL.S2 is used

as the limiter of capacity.

Under Configuration

SW.LG, set the logic state appropri-

ately for the action desired. Set the DL1.L and DL2.L configu-

rations. They can be set normally open or normally closed. For

example, if DL1.L is set to OPEN, the user will need to close

the switch to cause the control to limit capacity to the demand

limit 1 set point. Likewise, if DL1.L is set to CLSE (closed),

the user will need to open the switch to cause the control to

limit capacity to the demand limit 1 set point.
DEMAND LIMIT 4 TO 20 mA INPUT — Under Configu-

ration

DMD.L, set configuration DM.L.S to 2 (2 = 4 to

20 mA control). Under the same menu, set D.L.20 to a value

from 0 to 100% to set the demand limit range. For example,

with D.L.20 set to 50, a 4 mA signal will result in no limit to

the capacity and 20 mA signal will result in a 50% reduction in

capacity.

Demand Controlled Ventilation Control —

There are multiple methods for externally controlling the econ-

omizer damper.
IAQ DISCRETE INPUT CONFIGURATION — The IAQ dis-

crete input configuration requires a CEM module (optional) to

be installed and an interface to a switch input at TB5-13 and

14. The state of the input on the display can be found at

Inputs

AIR.Q

IAQ.I.

Before configuring the switch functionality, first determine

how the switch will be read. A closed switch can indicate either

a low IAQ condition or a high IAQ condition. This is set at

Configuration

SW.LG and IAQ.L. The user can set what a

low reading would mean based on the type of switch being

used. Setting IAQ.L to OPEN means that when the switch is

open the input will read LOW. When the switch is closed, the

input will read HIGH. Setting IAQ.L to CLSE (closed) means

that when the switch is closed the input will read LOW, and

therefore, when the switch is open the switch will read HIGH.

There are two possible configurations for the IAQ discrete

input. Select item Configuration

IAQ

AQ.CF

IQ.I.C

and configure for either 1 (IAQ Discrete) or 2 (IAQ Discrete

Override).
IQ.I.C = 1 (IAQ Discrete) — If the user sets IQ.I.C to 1 (IAQ

Discrete), and the switch logic (Configuration

SW.LG

IAQ.L) is set to OPEN, then an open switch reads low and a

closed switch reads high.

If the switch is open, the economizer will be commanded to

the IAQ Demand Vent Minimum Position.
These settings may be adjusted and are located at Configura-

tion

IAQ

DCV.C

IAQ.M.

If the switch is closed, the IAQ reading will be high and the

economizer will be commanded to the Economizer Minimum

Position.
This setting may be adjusted and is located at Configura-

tion

IAQ

DCV.C

EC.MN.