APPENDIX C — VFD INFORMATION

On variable air volume units with optional VFD, the supply

fan speed is controlled by a 3-phase VFD. The VFD is located

in the supply fan section behind a removable panel. The VFD

speed is controlled directly by the ComfortLink™ controls

through a 4 to 20 mA signal based on a supply duct pressure

sensor. The VFD has a display, which can be used for service

diagnostics, but setup of the building pressure and control loop

factors should be done through the scrolling marquee display.

The VFD is powered during normal operation to prevent

condensation from forming on the boards during the off mode

and is stopped by driving the speed to 0 (by sending a 4 mA

signal to the VFD).

The A Series units use ABB VFDs. The interface wiring for

the VFDs is shown in Fig. A. The VFD connects through

an isolation board to the 4 to 20 mA RCB board. Terminal

designations are shown in Table A. Configurations are shown

in Table B.

Table A — VFD Terminal Designations

TERMINAL

FUNCTION

U1
V1
W1

Three-Phase Main Circuit Input Power Supply

U2
V2

Three-Phase AC Output to Motor, 0 V to

W2

Maximum Input Voltage Level

X1-11 (GND)
X1-12 (COMMON)

Factory-supplied jumper

X1-10 (24 VDC)
X1-13 (DI-1)

Run (factory-supplied jumper)

X1-10 (24 VDC)

Start Enable 1 (Factory-supplied jumper). When

X1-16 (DI-4)

opened the drive goes to emergency stop.

X1-2 (AI-1)
X1-3 (AGND)

Factory wired for 4 to 20 mA remote input

Fig. A — VFD Wiring

A48-7712