60 Ton MCHX CIRCUIT A Charging Chart

All Compressors on a Circuit M ust be Operating

All Outdoor Fans M ust be Operating

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

145

150

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

Outdoor Air Temperature (deg F)

Sa

tu

ra

ted Conden

s

ing Temper

a

tu

re (deg F)

Reduce Charge if Above Curve

Add Charge if Below Curve

S S T= 4 5 F

S S T= 5 5 F

S S T= 3 5 F

60 Ton MCHX CIRCUIT B Charging Chart

All Compressors on a Circuit M ust be Operating

All Outdoor Fans M ust be Operating

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

145

150

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

Outdoor Air Temperature (deg F)

Sa

tu

ra

ted Conden

s

ing Temper

a

tu

re (deg F)

Reduce Charge if Above Curve

Add Charge if Below Curve

S S T= 4 5 F

S S T= 5 5 F

S S T= 3 5 F

Fig. 50 — Charging Chart — 48/50A2,A3,A4,A5060 with R-410A Refrigerant

LEGEND

MCHX— Microchannel Heat Exchanger
SST

Saturated Suction Temperature