beautypg.com

Carrier WEATHERMAKER 48/50AJ User Manual

Page 189

background image

CL-5

ITEM

EXPANSION

RANGE

DEFAULT

ENTRY

SW.LG

SWITCH LOGIC: NO / NC

FTS.L

Filter Status Inpt-Clean

Open/Close

Open

IGC.L

IGC Feedback - Off

Open/Close

Open

RMI.L

RemSw Off-Unoc-Strt-NoOv

Open/Close

Open

ECS.L

Economizer Switch - No

Open/Close

Open

SFS.L

Fan Status Sw. - Off

Open/Close

Open

DL1.L

Dmd.Lmt.Sw.1 - Off

Open/Close

Open

DL2.L

Dmd.Lmt.-Dehumid - Off

Open/Close

Open

IAQ.L

IAQ Disc.Input - Low

Open/Close

Open

FSD.L

Fire Shutdown - Off

Open/Close

Open

PRS.L

Pressurization Sw. - Off

Open/Close

Open

EVC.L

Evacuation Sw. - Off

Open/Close

Open

PRG.L

Smoke Purge Sw. - Off

Open/Close

Open

DISP

DISPLAY CONFIGURATION

TEST

Test Display LEDs

ON/OFF

Off

METR

Metric Display

ON/OFF

Off

LANG

Language Selection

0-1(multi-text strings)

0

PAS.E

Password Enable

ENABLE/DISABLE

Enable

PASS

Service Password

0000-9999

1111