Page 65

background image

Evco S.p.A.

c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114

page 65 of 74

8.3.4

Management of digital on/off dehumidifier

The zone controller c-pro 3 hecto MCZN has two digital inputs (one for each zone) on/off dehumidifiers.

If the digital input is at logic level "disabled", the corresponding additional dehumidifier will be considered in the OFF

state and all of its settings are disabled.

In order to make such control active, the inputs must be activated through the appropriate parameters maintainer.

8.4

Regulation of the DHW tank temperature for the DHW

water

(MCPS module)

8.4.1

Regulation principle

Whenever the c-pro 3 hecto MCPS module is present and enabled in the system, the system will automatically

consider the presence of a DHW storage tank in the system for the DHW.

With the presence of the DHW tank, the temperature regulation principle of the entire system will change significantly

in the following way:

-

WINTER REGULATION Via its utilities proposed for heating, the c-pro 3 CLIMA sistema, always keeps the

DHW tank at the pre-fixed temperature.

The delivery hot water for any heating requests of the Zones is withdrawn directly from the DHW tank.

-

SUMMER REGULATION: Via its utilities proposed for heating EXCEPT the heat pump, the c-pro 3 CLIMA

sistema, always keeps the DHW tank at the pre-fixed temperature.

The cool delivery water for any cooling requests from the Zones will be supplied by the chiller unit, obviously

without the use of the DHW tank.

8.4.2

Management of the DHW circuit circulation pump (MCPS

module)

The MCPS solar panels controller can manage a DHW tank with relative circulation pump.

The circulation pump is activated on temperature request of the DHW tank, whenever the heat pump or boiler utilities

are used to heat the DHW. When the use of the solar panel circuit/s for heating is sufficient, the DHW circulation

pump will not be used.

The activation of the DHW circulation pump will follow the delay times on switch-on established via the relevant

parameter.

As well as the request by the DHW tank, the DHW circulation pump can be activated during a special anti-grip or

antilegionella cycle.

The correct functioning of the circulation pumps is controlled via a digital input that can be configured as pump

protection input (thermal switch) or delivery flow switch (consult the relative explanatory paragraph).

This manual is related to the following products: