c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114
page 54 of 74
General parameters
Antilegionella
Setpoint
Water temperature set-point during the antilegionella
cycle
(expressed in °C)
70.0
0.0
150.0
General parameters
Antilegionella
Duration
Duration of the antilegionella cycle
(expressed in minutes)
60
0
255
MAINTENANCE
Panels Maintenance
Periodic cycle
Interval
Interval between two periodic activation cycles of the
solar panels circulation pumps
(expressed in minutes)
30
0
255
Panels MAINTENANCE
Periodic cycle
Duration
Duration of the periodic activation cycle of the solar
panels circulation pumps
(expressed in minutes)
10
0
255
Panels maintenance
Stag.emergency
Anti-stagnation emergency management mode
- ON/OFF = via a heat disposal ON-OFF valve
- Cover1 = via cover opening closing management (on
same relay contact)
- Cover2 = via cover opening closing management (on
two relay contacts)
ON/OFF
ON/OFF
Cover2
Panels maintenance
ON hyst.
Offset (differential) solar panels pump connection,
relative to work set-point.
(expressed in °C)
10.0
0.0
50.0
Panels maintenance
OFF hyst.
Offset (differential) solar panels pump disconnection,
relative to work set-point.
(expressed in °C)
5.0
-50.0
50.0
Panels maintenance
Temperature limits
HT setpoint
Solar panels circuit water high temperature alarm set-
point
(expressed in °C)
130.0
0.0
200.0
Panels maintenance
Temperature limits
HT hyst.
Solar panels circuit water high temperature alarm set-
point differential, relative to the high temperature
alarm set-point
(expressed in °C)
20.0
0.0
50.0
Panels maintenance
Temperature limits
LT setpoint
Solar panels circuit water low temperature alarm set-
point
(expressed in °C)
5.0
-10.0
40.0
Panels maintenance
Temperature limits
LT hyst.
Solar panels circuit water low temperature alarm set-
point differential, relative to the low temperature
alarm set-point
(expressed in °C)
5.0
0.0
10.0
AUX 1 MANAGEMENT
Aux 1 Maintenance
Mode
Auxiliary circuit 1 circulation pump regulation mode:
- CONT. = Continuous
- T.RICH. = On temperature request
T.RICH.
CONT.
T.RICH.
Aux 1 Maintenance
Contr. probe
Circuit
connected
with
AUX1
for
differential
temperature
control
for
AUX1circulation
pump
activation:
SOL
DHW
SOL