EVCO EPH4DXP1CT Installer manual User Manual

Page 55

background image

Evco S.p.A.

c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114

page 55 of 74

- DHW = heat exchange with DHW tank

- SOL = heat exchange with solar panel

Aux1 Maintenance

Setpoint

Auxiliary 1 circuit water temperature set-point

(expressed in °C)

60.0

35.0

80.0

Aux1 Maintenance

Hysteresis

Hysteresis (differential) for auxiliary circuit circulation

pump start

(expressed in °C)

5.0

0.0

20.0

Aux1 Maintenance

Offset ON

Temperature differential between control probe and

AUX1 probe for auxiliary circuit circulation pump

activation

(expressed in °C)

10.0

-50.0

50.0

Aux1 Maintenance

Offset OFF

Temperature differential between control probe and

AUX1 probe for auxiliary circuit circulation pump

deactivation

(expressed in °C)

5.0

-50.0

50.0

Aux1 Maintenance

Probe offset

Auxiliary circuit 1 probe calibration (offset)

(expressed in °C)

0.0

-10.0

10.0

Aux1 Maintenance

HT setpoint

Auxiliary circuit 1 high temperature alarm set-point

(expressed in °C)

70.0

0.0

90.0

Aux1 Maintenance

HT hyst.

High temperature alarm differential (Hysteresis)

relative to the high temperature alarm set-point

(expressed in °C)

5.0

0.0

10.0

Aux1 Maintenance

LT setpoint

Auxiliary circuit 1 low temperature alarm set-point

(expressed in °C)

10.0

-10.0

40.0

Aux1 Maintenance

LT hyst.

Low temperature alarm differential (Hysteresis)

relative to the low temperature alarm set-point

(expressed in °C)

5.0

0.0

10.0

Aux 1 Maintenance

Mode

Auxiliary circuit 1 circulation pump regulation mode:

- CONT. = Continuous

- T.RICH. = On temperature request

T.RICH.

CONT.

T.RICH.

DHW MANAGEMENT

DHW maintenance

Delay

Delay on activation of the DHW circuit pump

(expressed in seconds)

30

0

255

FLOW SWITCHES

Flow switches

Alr ON delay

Delay on activation of the flow switch alarm from

system start-up

(expressed in seconds)

3

0

0

255

Flow switches

Alr RUN delay

Delay on activation of the flow switch alarm with

system in normal conditions

(expressed in seconds)

5

0

255

Flow switches

Auto reset n°

Maximum number of flow switch alarms with

automatic rearm for passage to manual rearm

3

0

255