c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114

page 37 of 74

The machine On/Off key is the ESC key, pressed for about 2 seconds.

The remote On/Off input (when present) can be configured via the parameters:

-

PH02: Enables the function

-

PH34 : Sets the NC, NO logic for the digital contact

5.13.1

OFF state due to alarm

When the machine is on, a further state exists OFF due to alarm, which switches the nit and all devices off until the

alarm condition has been reset. If digital consent is missing in this state from supervisor or switch-off is requested

from key, the power plant goes into the relative OFF state. The alarms that cause this state are:

-

Delivery 1 probe alarm

-

Delivery 2 probe alarm

The machine works normally again when the alarm has been reset.

5.14

Summer/winter functioning mode

The operational mode can assume the following values:

E/I keyboard parameter Description

S= SUMMER

Summer functioning mode

W= WINTER

Winter functioning mode

There are procedures that allow to set the c-pro 3 CLIMA sistema functioning mode:

1)

Via the parameter regarding S/W keyboard in the maintenance menu

Setting - Be positioned on the S/W keyboard parameter and, pressing the ENTER key, modify the value using

the UP and DOWN keys. Confirm by pressing ENTER again.

2)

Via supervision protocol (function enabled by parameter PH03)

Setting - Send the operational mode change control via relative state from protocol.

This control has priority with respect to the S/W control from keyboard

3)

Using the Summer/Winter from digital input control PH03

Setting - With contact open the unit is in “winter” functioning mode, with contact closed in “summer”

functioning mode.

4)

Using Summer/Winter automatic switch-over function PH03

Setting - Switch-over from summer to winter takes place when the external temperature remains above the

value established with the PH05 parameter for the time established by the PH06 parameter

Conversely, switch-over from winter to summer takes place when the external temperature remains below

the value established with the PH04 parameter for the time established by the PH06 parameter

This control has priority with respect to the S/W control from digital input