6 unit status, 7 zones status – EVCO EPH4DXP1CT Installer manual User Manual
Page 48
Evco S.p.A.
c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114
page 48 of 74
0: ---
1: Zone ON/OFF
2: Zone alarm
3: Zone temperature external thermostat
4: Zone humidity external thermostat
PH58
Assignment DI1
1
---
6
PH59
Assignment DI2
2
---
6
PH60
Assignment DI3
3
---
6
PH61
Assignment DI4
4
---
6
PH62
Assignment DI5
5
---
6
PH63
Logic DI1
N.O.
N.O.
N.C.
PH64
Logic DI2
N.O.
N.O.
N.C.
PH65
Logic DI3
N.O.
N.O.
N.C.
PH66
Logic DI4
N.O.
N.O.
N.C.
PH67
Logic DI5
N.O.
N.O.
N.C.
MANUFACTOR PARAMETERS: DO
PH68
Logic DO1
N.O.
N.O.
N.C.
PH69
Logic DO2
N.O.
N.O.
N.C.
PH70
Logic DO3
N.O.
N.O.
N.C.
PH71
Logic DO4
N.O.
N.O.
N.C.
PH72
Logic DO5
N.O.
N.O.
N.C.
PH73
Logic DO6
N.O.
N.O.
N.C.
6.6
Unit status
The state controller MCZN is given by the state regulator central heat MCCT.
6.7
Zones status
There are two ways to change the status of regulation of the 6 areas:
1)
Using Remote On/Off Keyboard
Through the pages of the installer parameters.
2)
Using the commands On/Off from digital input for all 6 zones
Switch On: close contact with On/Off Remote zone: enabled if all other conditions are present, the regulation of the
zone switches to "ON".
Power Off: If the contact of the On/Off remote zone is open, the control zone goes OFF.