c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114

page 48 of 74

0: ---
1: Zone ON/OFF
2: Zone alarm
3: Zone temperature external thermostat
4: Zone humidity external thermostat

PH58

Assignment DI1

1

---

6

PH59

Assignment DI2

2

---

6

PH60

Assignment DI3

3

---

6

PH61

Assignment DI4

4

---

6

PH62

Assignment DI5

5

---

6

PH63

Logic DI1

N.O.

N.O.

N.C.

PH64

Logic DI2

N.O.

N.O.

N.C.

PH65

Logic DI3

N.O.

N.O.

N.C.

PH66

Logic DI4

N.O.

N.O.

N.C.

PH67

Logic DI5

N.O.

N.O.

N.C.

MANUFACTOR PARAMETERS: DO

PH68

Logic DO1

N.O.

N.O.

N.C.

PH69

Logic DO2

N.O.

N.O.

N.C.

PH70

Logic DO3

N.O.

N.O.

N.C.

PH71

Logic DO4

N.O.

N.O.

N.C.

PH72

Logic DO5

N.O.

N.O.

N.C.

PH73

Logic DO6

N.O.

N.O.

N.C.

6.6

Unit status

The state controller MCZN is given by the state regulator central heat MCCT.

6.7

Zones status

There are two ways to change the status of regulation of the 6 areas:

1)

Using Remote On/Off Keyboard

Through the pages of the installer parameters.

2)

Using the commands On/Off from digital input for all 6 zones

Switch On: close contact with On/Off Remote zone: enabled if all other conditions are present, the regulation of the

zone switches to "ON".

Power Off: If the contact of the On/Off remote zone is open, the control zone goes OFF.