5 system network page, 6 configuration parameters – EVCO EPH4DXP1CT Installer manual User Manual
Page 53
Evco S.p.A.
c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114
page 53 of 74
7.5
System Network page
From page network system controller MCPS you have the option to return to the application of thermal power plant
MCCT, as follows:
By pressing ESC key, the controller will go back all the same to the main display of the MCCT thermal power plant
controller.
7.6
Configuration parameters
Below find a list of all configuration parameters contained in the MAINTENANCE menu (maintenance technician) and
INSTALLER managed by the MCPS application.
A brief description is supplied for every parameter, the range of acceptable values, unit of measurement and the
default value proposed.
7.6.1
List of MAINTENANCE menu configuration parameters
Label
Parameter description
Default
Min
Max
GENERAL PARAMETERS
General parameters
Antigrip
Execution day
Antigrip function start day
Monday
Sunday
Saturday
General parameters
Antigrip
Execution hour
Antigrip function start time
2:00
0:00
23:00
General parameters
Probes offset
Upper DHW tank
Boiler upper probe calibration (offset)
(expressed in °C)
0.0
-10.0
10.0
General parameters
Probes offset
Lower DHW tank
Boiler lower probe calibration (offset)
(expressed in °C)
0.0
-10.0
10.0
General parameters
Antilegionella
Enable
Enabling of antilegionella cycle
No
No
Yes
General parameters
Antilegionella
Mode
Antilegionella cycle activation mode
- MONTH = Monthly
- WEEK = Weekly
- DAY = Daily
WEEK
MONTH
DAY
General parameters
Antilegionella
Start hour
Time of antilegionella cycle start
(expressed in hours:minutes)
16:00
0:00
23:00
General parameters
Antilegionella
Day week
Day of the week for antilegionella cycle start
(if weekly activation enabled)
Wednes-
day
Sunday
Saturday
General parameters
Antilegionella
Day month
Day of the month for antilegionella cycle start
(if monthly activation enabled)
15
1
28