3.4.1

MCCT thermal power plant controller network configuration

The controller of thermal power plant (the logical center of the controlled), you must first set the number of zone

controllers MCZN will be present in the system, using the following procedure:

1.

Enter the Installer

General parameters menu of the MCCT regulator

2.

Set the total number of zones controlled and the number of MCZN zone regulators present in the system

3.

To set the communication speed (125k suggested) go to the menu

Installer -> general parameters and modify the baud rate parameter.

3.4.2

Network Configuration zone modules MCZN

The zone regulator leaves the factory configured as zone 1 module (therefore with CANbus 2 address).

Whenever it is necessary to install more than one zone controller in the system, it will be necessary to configure the

regulators present as zone regulators 2, 3, etc…up to a maximum of 8.

To change the network configuration of the MCZN zone module network, follow the procedure below:

1.

Connect a zone regulator to the CANbus network (leaving all of the other zone regulators disconnected from

the network);the controller connected will be recognised as zone 1 controller

2.

Access the MCZN zone regulator application

3.

Enter the Installer

General parameters menu

4.

Set the number of local zones managed by the MCZN regulator

5.

Set the number of the last zone regulator that is to be inserted in the system managed (e.g. zone 4 regulator).

6.

The controller will automatically assume the appropriate CANbus address

7.

Repeat the operation, connecting the next to last zone controller to the CANbus network and so on, until the

second zone regulator is connected (zone 2 regulator).

3.4.3

MCPS solar panels controller network configuration

The controller for solar panels MCPS is the sole controller of this type can be installed in the plant, for its configuration

will be sufficient to enable the presence of the regulator MCPS by the application of thermal power plant, with the

following procedure:

1.

Enter the Installatore

Parametri generali (Installer, General parameters) menu of the MCCT regulator

2.

Enable the presence of the MCPS regulator in the system

3.5

Displays network configuration

For the final user, the c-pro 3 CLIMA sistema envisions the use of a series of user terminals installed in zone, from

which it is possible to display temperature, humidity, state of the zone and set the work set-points, time bands, etc.

The maximum number of user terminals that can be set in the system depends mainly on the configuration of the

terminal selected by the installer, from the following possibilities:

Public terminal Vgraph (maximum n°1 display for the entire system)

Module private terminal (maximum n°8 displays for the entire system)

Zone private terminal

Depending on the type of terminal desired, settings must be made in the MCZN zone controller and in the Vroom user