5.12
Configuration parameters
The following task map lists all the configuration parameters contained in the user menu, maintainer, installer and
manufacturer.
For each parameter is also provided a brief description, the range of permissible values, the unit of measure and the
default value proposed.
The menus are structured according to the logic stated in the corresponding sections described above.
5.12.1
List of configuration parameters
Label
Parameter description
Default
Min
Max
USER PARAMETERS
ONOFF
State of the unit
OFF
0: OFF
1: ON
Mode
Season mod.
Winter
0:Winter
1:Summer
MAINTENANCE PARAMETERS: HOURS
PM01
Pump operation time alarm
20000
0
65535
PM02
Line 1 pump operation time
0
0
65535
PM03
Line 2 pump operation time
0
0
65535
PM04
Line 3 pump operation time
0
0
65535
PM05
Line 4 pump operation time
0
0
65535
PM06
Line 5 pump operation time
0
0
65535
PM07
Line 6 pump operation time
0
0
65535
PM08
Boiler operation time alarm
20000
0
65535
PM09
Boiler operation time
0
0
65535
PM10
Chiller-Heat pump operation time alarm
20000
0
65535
PM11
Chiller-Heat pump operation time
0
0
65535
MAINTENANCE PARAMETERS: MANUAL
PM30
Enable manual operation line 1 pump
Disab.
0:Disab.
1:Enab.
PM31
Force manual line 1 pump
OFF
OFF
ON
PM32
Enable manual operation line 2 pump
Disab.
0:Disab.
1:Enab.
PM33
Force manual line 2 pump
OFF
OFF
ON
PM34
Enable manual operation line 3 pump
Disab.
0:Disab.
1:Enab.
PM35
Force manual line 3 pump
OFF
OFF
ON
PM36
Enable manual operation line 4 pump
Disab.
0:Disab.
1:Enab.
PM37
Force manual line 4 pump
OFF
OFF
ON
PM38
Enable manual operation line 5 pump
Disab.
0:Disab.
1:Enab.
PM39
Force manual line 5 pump
OFF
OFF
ON
PM40
Enable manual operation line 6 pump
Disab.
0:Disab.
1:Enab.
PM41
Force manual line 6 pump
OFF
OFF
ON
PM42
Enable manual HP
Disab.
0:Disab.
1:Enab.
PM43
Force manual HP
OFF
OFF
ON
PM44
Enable manual boiler
Disab.
0:Disab.
1:Enab.
PM45
Force manual boiler
OFF
OFF
ON
PM46
Enable manual chiller
Disab.
0:Disab.
1:Enab.
PM47
Force manual chiller
OFF
OFF
ON
MAINTENANCE PARAMETERS: ENABLING
PM51
Enabling MCZN1
YES
NO
YES
PM52
Enabling MCZN2
YES
NO
YES
PM53
Enabling MCZN3
YES
NO
YES
PM54
Enabling MCZN4
YES
NO
YES
PM55
Enabling MCZN5
YES
NO
YES
PM56
Enabling MCZN6
YES
NO
YES
PM57
Enabling MCZN7
YES
NO
YES
PM58
Enabling MCZN8
YES
NO
YES
MAINTENANCE PARAMETERS: ANTIGRIP
PM20
Enable pumps antigrip
Enab.
Disab.
Enab.
PM21
Enable mixing valve antigrip
Enab.
Disab.
Enab.
PM22
Week day for antigrip
Ven.
Dom.
Sab.
PM23
Hour for antigrip
2
0
23
MAINTENANCE PARAMETERS: OFFSET
PM80
Offset delivery 1
0.0
-10.0
10.0
PM81
Offset delivery 2
0.0
-10.0
10.0
PM82
Offset delivery 3
0.0
-10.0
10.0