5.12

Configuration parameters

The following task map lists all the configuration parameters contained in the user menu, maintainer, installer and

manufacturer.

For each parameter is also provided a brief description, the range of permissible values, the unit of measure and the

default value proposed.

The menus are structured according to the logic stated in the corresponding sections described above.

5.12.1

List of configuration parameters


Label

Parameter description

Default

Min

Max

USER PARAMETERS

ONOFF

State of the unit

OFF

0: OFF

1: ON

Mode

Season mod.

Winter

0:Winter

1:Summer

MAINTENANCE PARAMETERS: HOURS

PM01

Pump operation time alarm

20000

0

65535

PM02

Line 1 pump operation time

0

0

65535

PM03

Line 2 pump operation time

0

0

65535

PM04

Line 3 pump operation time

0

0

65535

PM05

Line 4 pump operation time

0

0

65535

PM06

Line 5 pump operation time

0

0

65535

PM07

Line 6 pump operation time

0

0

65535

PM08

Boiler operation time alarm

20000

0

65535

PM09

Boiler operation time

0

0

65535

PM10

Chiller-Heat pump operation time alarm

20000

0

65535

PM11

Chiller-Heat pump operation time

0

0

65535

MAINTENANCE PARAMETERS: MANUAL

PM30

Enable manual operation line 1 pump

Disab.

0:Disab.

1:Enab.

PM31

Force manual line 1 pump

OFF

OFF

ON

PM32

Enable manual operation line 2 pump

Disab.

0:Disab.

1:Enab.

PM33

Force manual line 2 pump

OFF

OFF

ON

PM34

Enable manual operation line 3 pump

Disab.

0:Disab.

1:Enab.

PM35

Force manual line 3 pump

OFF

OFF

ON

PM36

Enable manual operation line 4 pump

Disab.

0:Disab.

1:Enab.

PM37

Force manual line 4 pump

OFF

OFF

ON

PM38

Enable manual operation line 5 pump

Disab.

0:Disab.

1:Enab.

PM39

Force manual line 5 pump

OFF

OFF

ON

PM40

Enable manual operation line 6 pump

Disab.

0:Disab.

1:Enab.

PM41

Force manual line 6 pump

OFF

OFF

ON

PM42

Enable manual HP

Disab.

0:Disab.

1:Enab.

PM43

Force manual HP

OFF

OFF

ON

PM44

Enable manual boiler

Disab.

0:Disab.

1:Enab.

PM45

Force manual boiler

OFF

OFF

ON

PM46

Enable manual chiller

Disab.

0:Disab.

1:Enab.

PM47

Force manual chiller

OFF

OFF

ON

MAINTENANCE PARAMETERS: ENABLING

PM51

Enabling MCZN1

YES

NO

YES

PM52

Enabling MCZN2

YES

NO

YES

PM53

Enabling MCZN3

YES

NO

YES

PM54

Enabling MCZN4

YES

NO

YES

PM55

Enabling MCZN5

YES

NO

YES

PM56

Enabling MCZN6

YES

NO

YES

PM57

Enabling MCZN7

YES

NO

YES

PM58

Enabling MCZN8

YES

NO

YES

MAINTENANCE PARAMETERS: ANTIGRIP

PM20

Enable pumps antigrip

Enab.

Disab.

Enab.

PM21

Enable mixing valve antigrip

Enab.

Disab.

Enab.

PM22

Week day for antigrip

Ven.

Dom.

Sab.

PM23

Hour for antigrip

2

0

23

MAINTENANCE PARAMETERS: OFFSET

PM80

Offset delivery 1

0.0

-10.0

10.0

PM81

Offset delivery 2

0.0

-10.0

10.0

PM82

Offset delivery 3

0.0

-10.0

10.0