Wait Input Function

The wait input is a NON-SAFETY-RELATED function.
This function puts the OSSD into an OFF state through a signal from an external device (non safety-
related device).
See

"Functions" (page 2-4) for the information of wiring system and cable type to activate this function.

How to use

(1) The signal from the external non safety-related control device is connected to the wait input. When

this signal is ON, the OSSD of the GL-RHG goes to OFF.

(2) This function is useful for testing and making sure that the machine which the GL-RHG is installed on

can stop within the specified period of time when the OSSD goes into an OFF state.

Point

The OSSD goes into an OFF state when the wait input is activated while the GL-RHG is in the
muted condition. The GL-RHG returns to normal operation after the wait input is deactivated.

"Muting function" (page 2-7)

Wiring

Point

The switch must be rated at 24 V DC, 2 to 3 mA.

Time chart

Reference

For the GL-RHG, the 7-segment display indicates "" if the wait input is activated.
See

"Function Indicators and 7-segment Display" (page 5-2)

DANGER

The wait output is not allowed to be connected to the safety output provided from the
safety-related control system. Connection to the safety output of the safety-related control
system may result in significant harm to the machine operators including serious injury or
death.

When using a PNP output type cable

When using an NPN output type cable

Brown

White

Blue

GL-RHG

Transmitter

+24 V

0 V

Short-circuit current: 2.5 mA

Brown

White

Blue

+24 V

0 V

Short-circuit current: 2.5 mA

GL-RHG

Transmitter

Wait input

GL-RHG

OSSD

60 ms max.

60 ms max.

ON

OFF

ON

OFF

No interruption

Interruption