1 troubleshooting, Error condition, Troubleshooting – KEYENCE GL-RHG Series User Manual
Page 126
A-2
GL-RHG-M-NOA-E
App
end
ix
1
Troubleshooting
If the GL-RHG is not functioning normally, check the GL-RHG indicators first.
The GL-RHG is in an error condition under the following situations.
•
The center indicators blink in red.
•
The 7-segment display indicates "".
If the GL-RHG does not demonstrate the above situations, the GL-RHG is not in an error condition.
Error condition
The GL-RHG performs self-diagnosis for approx. 2 seconds after the power is turned on and checks for
errors. Self-diagnosis is also performed periodically during normal operations.
If the self-diagnosis function detects an error, the GL-RHG goes to an error condition and the OSSD is
kept in the OFF state even if no interruption exists in the protective zone. The indicators operate in the fol-
lowing manner during an error condition.
7-segment display
: Indication corresponding to the cause of the error
Center indicators
: All indicators are blinking in red.
Error output
: OFF
To release the error condition, first remove the cause of the error, and then either activate the reset input
or turn the power off and on again.
Self-diagnosis description
Transmitter
Receiver
7-segment display
Function indicator
Transmitter
•
Error in the external power supply voltage
•
Failure in the internal power supply circuit
•
Failure in the light emitting element or light
receiving circuit
•
CPU overdrive
•
Memory error
•
Cable open/short-circuit
Receiver
•
Error in the external power supply voltage
•
Failure in the internal power supply circuit
•
Failure in the light receiving element or detec-
tion circuit
•
CPU overdrive
•
Memory error
•
Failure in the safety output circuit (OSSD)
•
Cable open/short-circuit
•
Program monitoring