Time chart – KEYENCE GL-RHG Series User Manual
Page 33
![background image](/manuals/658037/33/background.png)
2-5
Temporary Suspension of Safety Function
2-9
GL-RHG-M-NO2-E
Fu
nct
ion
s and
Feat
ures
2
Time chart
T1: 0.04 to 3 seconds
Point
•
If muting input 2 turns on outside the T1 range after muting input 1 turns on, the GL-RHG
will not mute and remains in normal operation. (The GL-RHG does not go into an error
condition.)
•
If only muting input 1 or muting input 2 turn OFF and back ON, the GL-RHG will not return to
the muted condition. To return to the muted condition, both muting inputs 1 and 2 must first
turn OFF and the muting conditions must be met again.
•
If the GL-RHG power is turned ON while the GL-RHG is in the muted condition or either
muting input 1 or 2 is on, the GL-RHG will not go to a muted condition. In this case, both
muting inputs must be turned OFF and the muting conditions must be met again.
Reference
•
The function indicators and 7-segment display indicate each condition.
"Function Indicators and 7-segment Display" (page 5-2)
•
If the GL-RHG does not go to muted condition when both muting input 1 and 2 are ON, all muting
condition are not met. The configuration software can show the conditions which are not met.
Muting input 1
Muting input 2
Muted condition
Not muted condition
Muting lamp
GL-RHG
OSSD
T1
T1
No limit
5 ms max.
5 ms max.
90 ms max.
Within 5 min
90 ms max.
90 ms max.
Within 5 min
90 ms max.
Response time (ON to OFF)
Response time (OFF to ON)
Clear
Blocked
ON
OFF
ON
OFF
ON
OFF
Light OFF
Light ON