2-5
Temporary Suspension of Safety Function
2-21
GL-RHG-M-NO2-E
Fu
nct
ion
s and
Feat
ures
2
Conditions for initiation of override
The override condition is initiated if all of the following conditions are met and the wait input goes to the
ON state within 0.04 to 1 s after the override input turns ON.
•
The GL-RHG is not an error condition.
•
OSSD is in the OFF state.
•
GL-RHG detects interruption in the protective zone. (One or more beam axis is blocked.)
•
Either of muting inputs, or both, turns ON state.
Conditions for termination of override
The override condition is terminated if one of the following conditions is met.
•
All of muting inputs turn OFF
•
Either the override input or wait input, or both, turn OFF.
•
GL-RHG goes into the error condition.
•
Maximum override period of approx. 60 seconds has been passed.
Time chart
DANGER
•
The installation of the indication for override may be required by the laws, rules,
regulations, and standards in the country or region in which the GL-RHG is used if you
apply the override function. It depends on the machine application and/or the result of
your risk assessment. If it is necessary for you to provide the indication for override, you
must fulfill the requirements because you are fully responsible for installation of the
indication for override.
•
Only the responsible personnel must be allowed use or activation of the override
function.
•
Those who use the override function must fulfill all requirements related to the override
function. KEYENCE accepts NO responsibility and NO liability for any damage or any
injury due to the unauthorized installation, usage, or maintenance, which are not
specified in this user's manual, and/or due to noncompliance with the laws, rules,
regulations and standards in the country or region in which the GL-RHG is used.
Muting input 1
Muting input 2
GL-RHG
Override input
Reset input
Muting lamp
OSSD
ON
OFF
Clear
Blocked
ON
OFF
ON
OFF
ON
OFF
Override condition
No override condition
ON
OFF
Light ON
Light OFF
No limit
No limit
Within approx. 60 s
Within
0.04 to 1 s
90 ms max.
90 ms max.