beautypg.com

2 data processing time, Data proc, Data processing time -3 – KEYENCE DL-EP1 User Manual

Page 89: Data processing time

background image

4-3

4

Sp
ec

ific

ati

ons

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -

4-2

Data Processing Time

This section describes the length of time that lasts from detection by a sensor to data

processing by PLC.

Maximum data processing time = (1) + (2) + (3) + (4)

(1)PLC scan time

(2)RPI (Transmission cycle)

(3)DL-EP1 data communication time

(4)Sensor amplifier response time

(2)RPI is set with the scanner unit. It can be set in 0.5 ms increments between 0.5 ms

and 10000 ms.

(3)DL-EP1 data communication time

The time required for sending outputs and current value data from a sensor

amplifier to the DL-EP1 is as follows:

Sensor amplifier with calculation function OFF, or sensor amplifier with no

calculation function

Number of connected sensor

amplifiers

Output, judgment value, or

current value

1

7.8 ms

2

9.8 ms

3

13.8 ms

4

15.8 ms

5

19.8 ms

6

21.8 ms

7

25.8 ms

8

27.8 ms

CPU unit

EtherNet/IP

scanner

DL-EP1

Sensor amplifier

(1)

(2)

(3)

(4)