3-4 Message Communication

3-35

3

Communi

cat
in

g wit

h the

IL Seri

es

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -

00H

77H

(119)

Output4

(Alarm output)

Indicates the status of alarm output (output 4)

of each amplifier. When alarm is output, the bit

corresponding to the ID number of the sensor

amplifier is turned ON.

Bit 0 to bit 7: ID number 1 to ID number 8

Bit 8 to bit 15: Reserved for system

R

WORD

78H(120

)

Output5

(Unassigned)

(Unassigned)

79H

(121) to

89H

(137)

Reserved for system

8AH

(138)

Current Value 0

Invalid

When the current value 0 of each amplifier is

invalid, the bit of corresponding ID number is

turned ON.

Bit 0 to bit 7: ID number 1 to ID number 8

Bit 8 to bit 15: Reserved for system

R

WORD

8BH

(139)

Current Value 0

Under Range

When the current value 0 of each amplifier is

less than the lower limit of the detection range,

the bit of the corresponding ID number is

turned ON.

Bit 0 to bit 7: ID number 1 to ID number 8

Bit 8 to bit 15: Reserved for system

R

WORD

8CH

(140)

Current Value 0

Over Range

When the current value 0 of each amplifier is

higher than the upper limit of the detection

range, the bit of corresponding ID number is

turned ON.

Bit 0 to bit 7: ID number 1 to ID number 8

Bit 8 to bit 15: Reserved for system

R

WORD

8DH

(141)

Current Value 1

Invalid

(Unassigned)

R

WORD

8EH

(142)

Current Value 1

Under Range

(Unassigned)

R

WORD

8FH

(143)

Current Value 1

Over Range

(Unassigned)

R

WORD

90H

(144)

Current Value 0

(ID Number 1)

Indicates the current value 0 of the sensor of

ID number 1.

Parameter range:

-2147483648 to 2147483647

R

DINT

91H

(145) to

96H

(150)

:

97H

(151)

Current Value 0

(ID Number 8)

Indicates the current value 0 of the sensor ID

number 8.

Parameter range:

-2147483648 to 2147483647

R

DINT

98H

(152) to

AFH

(175)

Reserved for system

B0H

(176)

Sensor Status

Mask Setting

Set up the condition to determine if the sensor

error or warning is the recoverable DL-EP1

error (MS LED blinks in red). If mask is

selected, MS LED does not blink in red when

a sensor error or warning occurs.

Parameter range: 0 to 1 (initial value: 0)

0: Not mask

1: Mask

R/W

UINT

Instance

ID

Attribute

ID

Name

Description

Attribute

Data

Type