Page 69

background image

3-4 Message Communication

3-39

3

Communi

cat
in

g wit

h the

IL Seri

es

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -

Group1

0337H

(823)

Reset request

result

Indicates the result of reset.

Parameter range: 0 to 2

0:Executing

1:Normal termination

2:Abnormal termination

R

DINT

0338H

(824)

Current system

parameters

*6

Indicates the current status of the system

parameters. Use this attribute to check the

system parameters with which the sensor

amplifier is actually operating.

The corresponding bit turns on according to

the current status.

bit 0:

0:NPN

1:PNP

bits 1, 2 and 3 (For main unit only. Fixed to

000 for expansion unit)

000: Analog output OFF

001: 0 to 5 V

010: -5 to +5 V

011: 1 to 5 V

100: 4 to 20 mA

R

DINT

0339H

(825) to

033BH

(827)

(Reserved for system)

033CH

(828)

Tuning result

*7

Indicates the result of tuning.

Parameter range: 0 to 2

0:Executing

1:Normal termination

2:Abnormal termination

R

DINT

033DH

(829)

Calibration result

Indicates the result of calibration.

Parameter range: 0 to 2

0:Executing

1:Normal termination

2:Abnormal termination

R

DINT

033EH(8

30)

(Reserved for system)

033FH

(831)

(Reserved for system)

Group2

0340H

(832)

Group2 Entry

count

Indicates the No. of Group 2 entries.

Parameter range: 20

R

DINT

0341H

(833)

HIGH setting

value

(BANK 0)

*2

Set up setting value of HIGH side (BANK 0).

Parameter range: -99.999 to +99.999

(initial value: +5.000)

R/W

DINT

0342H

(834)

LOW setting

value

(BANK 0)

*2

Set up setting value of LOW side (BANK 0).

Parameter range: -99.999 to +99.999

(initial value: -5.000)

R/W

DINT

0343H

(835)

Shift target

value

(BANK 0)

*2

Set up target value of shift (BANK 0).

Parameter range: -99.999 to +99.999

(initial value: 0)

R/W

DINT

0344H

(836)

Analog output -

upper limit value

(BANK 0)

*2, *9

Set up upper limit of analog output (BANK 0).

(Main unit only)

Parameter range: (Main unit only)

-99.999 to +99.999

(initial value: +10.000)

R/W

DINT

0345H

(837)

Analog output -

lower limit value

(BANK 0)

*2, *9

Set up lower limit of analog output (BANK 0).

(Main unit only)

Parameter range: -99.999 to +99.999

(initial value: 1.0000)

R/W

DINT

Class

Attribute

ID

Name

Description

Attribute

Data

Type