Assignment to out area (scanner to dl-ep1), Assignment to out area (scanner to dl-ep1) -16 – KEYENCE DL-EP1 User Manual
Page 46
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -
3-3 Cyclic communication
3-16
3
Communi
cat
in
g wit
h the
IL Seri
es
Warning code list
No warning code occurs in the DL-EP1 and in the IL Series sensor amplifiers
connected to the DL-EP1.
The data to the sensor amplifier is assigned to the OUT area of the EtherNet/IP
scanner.
External Input (5 Words (10 Bytes)) assembly instance (Instance ID): 65H
ID numbers (ID01 to ID08) are assigned for each sensor amplifier according to the
number of sensor amplifiers. The ID numbers larger than the number of connected
sensor amplifiers and ID09 to ID15 are not assigned.
* You use the external inputs by assigning specific functions. For details of the
functions to be assigned, refer to “IL Series User's Manual”.
Assignment to OUT Area (Scanner to DL-EP1)
DL-EP1 data
Scanner's OUT area
Address 0
Address 1
Address 9
External Input
(Assembly Instance: 101)
1-byte (8-bit) data
Name
Address
(Byte)
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
External
Input
Request 1
(External
Input 1)
0
ID08
. . . . .
ID01
1
Reserved for
system
ID15
. . . . .
ID09
External
Input
Request 2
(External
Input 2)
2
ID08
. . . . .
ID01
3
Reserved for
system
ID15
. . . . .
ID09
External
Input
Request 3
(External
Input 3)
4
ID08
. . . . .
ID01
5
Reserved for
system
ID15
. . . . .
ID09
External
Input
Request 4
(External
Input 4)
6
ID08
. . . . .
ID01
7
Reserved for
system
ID15
. . . . .
ID09
External
Input
Request 5
(Unassigned)
8
ID08
. . . . .
ID01
9
Reserved for
system
ID15
. . . . .
ID09