4 message communication, Communi cat in g wit h the il seri es – KEYENCE DL-EP1 User Manual
Page 68
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -
3-4 Message Communication
3-38
3
Communi
cat
in
g wit
h the
IL Seri
es
Group1
032AH
(810)
Analog output
value
Indicates the current analog output value.
(main unit only)
Parameter range:
Voltage: -5.000 to +5.000 (+5.500 for error)
4 to 20 mA: +4.00 to +20.00 (+3.00 for error)
OFF: Fixed to 0
R
DINT
032BH
(811)
Bank status
Indicates the currently active bank No.
Use this attribute to check the bank No. for
which the sensor amplifier is actually
operating.
Parameter range: 0 to 3
0: Bank 0
1: Bank 1
2: Bank 2
3: Bank 3
R
DINT
032CH
(812)
Timing status
Indicates the currently active timing status.
Use this attribute to check the timing status
under which the sensor amplifier is actually
operating.
Parameter range: 0 to 1
0: During Sampling
1: Not during sampling
R
DINT
032DH
(813) to
0331H
(817)
(Reserved for system)
0332H
(818)
Laser emission
stop status
Indicates the currently active laser emission
stop status.
Use this attribute to check the laser emission
stop status under which the sensor amplifier is
actually operating.
Parameter range: 0 to 1
0:Laser emitting
1:Laser stopped (Emission stop input ON/
Laser error/Sensor head error)
R
DINT
0333H
(819)
Abnormal
setting
*3
Indicates an abnormal setting status.
Parameter range: 0 to 1
0:Normal setting
1:Abnormal setting
R
DINT
0334H
(820)
External input
status
Indicates the external input status. When the
external input cable of the sensor amplifier or
the external input of the cyclic communication
is on, the corresponding bit turns on.
This operation is enabled even when "Not
used" is selected for the function setting of
external inputs 1 through 4.
Bit0:External input 1
Bit1:External input 2
Bit2:External input 3
Bit3:External input 4
R
DWORD
0335H
(821)
EEPROM write
result
*4
Indicates the result of writing to EEPROM.
Parameter range: 0 to 2
0:Writing
1:Normal termination
2:Abnormal termination
R
DINT
0336H
(822)
Zero shift/Zero
shift reset
result
*5
Indicates the result of zero shift or zero shift
reset.
Parameter range: 0 to 2
0:Executing
1:Normal termination
2:Abnormal termination
R
DINT
Class
Attribute
ID
Name
Description
Attribute
Data
Type