3-4 Message Communication
3-37
3
Communi
cat
in
g wit
h the
IL Seri
es
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -
Attributes for IL Series
Designate the ID number (01H to 08H) of a sensor amplifier as the instance ID.
When the parameter range includes decimal data, a value should be read or
written as an integer by ignoring the decimal point. For example, when writing
"+1.235" as the HIGH-side setting value (BANK 0), write "+1235".
Class
Attribute
ID
Name
Description
Attribute
Data
Type
Group1
0320H
(800)
Group1
Entry count
Indicates the number of items (entries) that
can be set in Group 1.
Parameter range: 29
R
DINT
0321H
(801)
Sensor amplifier
error
*1
Indicates the error status of the sensor
amplifier.
When an error occurs, the corresponding bit
turns on.
bit0: Overcurrent error
bit1: EEPROM error
bit2: Head error
bit7: Spot light laser error
bit8: Incompatible model error
bit11: Amplifier communication error
bit12: Number-of-units error
bit13: Calculation error
Other than above: Fixed to 0
R
DWORD
0322H
(802)
(Reserved for system)
0323H
(803)
(Reserved for system)
0324H
(804)
Judgment
output/Alarm
output
Indicates the output status of the sensor.
When an output is on, the corresponding bit
turns on.
Bit0:HIGH judgment output
Bit1:LOW judgment output
Bit2:GO judgment output
Bit3:Alarm output
R
DWORD
0325H
(805)
Judgment value
(P.V. Value)
*2,
Indicates the judgment value (P.V. value).
Parameter range: -99.999 to +99.999
R
DINT
0326H
(806)
Internal
measurement
value
(R.V. value)
*2
Indicates the internal measurement value
(R.V. value).
Parameter range:-99.999 to +99.999
R
DINT
0327H
(807)
Peak hold value
during hold
period
*2
•
In the mode other than the sample hold
mode
Indicates the peak-hold value during the
sampling period.
Parameter range:
-99.999 to +99.999
•
In the sample hold mode
Parameter range: -99.998
R
DINT
0328H
(808)
Bottom hold
value during
hold
period
*2
•
In the mode other than the sample hold
mode
Indicates the bottom-hold value during the
sampling period.
Parameter range:
-99.999 to +99.999
•
In the sample hold mode
Parameter range: -99.998
R
DINT
0329H
(809)
Calculation
value
(CALC value)
*2
Indicates calculation value (CALC value).
Parameter range: -99.999 to +99.999
R
DINT