APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — SET POINTS
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
SETPOINT CONFIGURATION
SETPOINTS
SET_PNT
OCSP
Occupied Cool Setpoint
55 to 80
°F
78
OCSP
UCSP
Unoccupied Cool Setpoint
65 to 95
°F
85
UCSP
OHSP
Occupied Heat Setpoint
55 to 80
°F
68
OHSP
UHSP
Unoccupied Heat Setpoint
40 to 80
°F
60
UHSP
GAP
HeatCool Setpoint Gap
2 to 10
^F
5
HCSP_GAP
STO.R
SPT Offset Range (+/)
0 to 5
^F
5
SPTO_RNG
RH.SP
Space RH Occupied SP
30 to 100
%
50
SPRH_SP
RH.UN
Space RH Unoccupied SP
30 to 100
%
50
SPRH_USP
RH.DB
Space RH Deadband
2 to 20
%
8
SPRH_DB
RH.HB
Reheat Heat SP Deadband
5 to 5
^F
2
RH_HSPDB
CA.LO
Circuit A Lockout Temp
0 to 100
°F
0
OATLCMPA
CB.LO
Circuit B Lockout Temp
0 to 100
°F
0: no HumidiMiZer FIOP
HumidiMiZer FIOP:
40 (PG0816)
0 (2028, PM16)(0307)
OATLCMPB
CC.LO
Circuit C Lockout Temp
0 to 100
°F
0
OATLCMPC
HT.LO
Heating Lockout Temp
40 to 125
°F
75
OATLHEAT
EH.LO
Econo Cool Hi Temp Limit
40 to 100
°F
65
OATLECLH
EL.LO
Econo Cool Lo Temp Limit
30 to 50
°F
0
OATLECLL
FC.LO
Free Cool Low Temp Limit
30 to 70
°F
50
OATLUEFC
LCSP
Low Cool SAT Setpoint
55 to 75
°F
55 (0307)
65 (0828)
LCSASP
HCSP
High Cool SAT Setpoint
50 to 70
°F
55
HCSASP
MODE — INPUTS
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
STATUS DISPLAY
INPUTS
UINPUT
STAT
Thermostat Inputs
Y1
Thermostat Y1 Input
On/Off
Y1
forcible
Y2
Thermostat Y2 Input
On/Off
Y2
forcible
W1
Thermostat W1 Input
On/Off
W1
forcible
W2
Thermostat W2 Input
On/Off
W2
forcible
G
Thermostat G Input
On/Off
G
forcible
GEN.I
General Inputs
FIL.S
Filter Status Switch
Dirty/Clean
FILTSTAT
forcible
FAN.S
Fan Status Switch
On/Off
FAN_STAT
forcible
FDWN
Fire Shutdown Switch
On/Off
FIREDOWN
forcible
ENTH
Outdoor Enthalpy Switch
High/Low
ENTHALPY
forcible
RM.OC
Remote Occupancy Switch
On/Off
REM_OCC
forcible
HUM
Space Humidity Switch
High/Low
HUM_STAT
forcible
CS.IN
Current Sensor Inputs
CS.A1
Compressor A1 Feedback
On/Off
CS_A1
CS.A2
Compressor A2 Feedback
On/Off
CS_A2
CS.B1
Compressor B1 Feedback
On/Off
CS_B1
CS.C1
Compressor C1 Feedback
On/Off
CS_C1
AIR.Q
Air Quality Inputs
IAQ.S
IAQ Level (switch)
High/Low
IAQIN
forcible
forcible
IAQ
IAQ Level (sensor)
xxxx
ppm
IAQ
forcible
forcible
OAQ
OAQ Level (sensor)
xxxx
ppm
OAQ
forcible
forcible
SP.RH
Space Humidity Sensor
xxx.x
%
SPRH
forcible
forcible
48/50PG and PM