APPENDIX A — LOCAL DISPLAY AND CCN TABLES

MODE — RUN STATUS

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/

SUB­TABLE

CCN POINT

CCN

WRITE

STATUS

MENU

WRITE

STATUS

RUN STATUS

STATUS DISPLAY

VIEW

Auto View of Run Status

(VIEW = Display only)

HVAC

HVAC Mode Status

1=Disabled
2=Ventilation
3=Cool
4=Heat

HVACMODE

OCC

Currently Occupied

No/Yes

OCCUPIED

SAT

Suppy Air Temperature

xxx..x

°F

SAT_DISP

ALRM

Current Alarms & Alerts

xx

ALRMALRT

TIME

Time of Day

xx.xx

hh.mm

TIMECOPY

VERS

Software Version Numbers

VERSIONS

MBB

CESR131320­xx­xx

(xx­xx in table)

MODEL_NUMBER_01

ECB

CESR131249­xx­xx

MODEL_NUMBER_02

MARQ

CESR131171­xx­xx

MODEL_NUMBER_03

MODE

Control Modes

MODEDISP

SYS

Current System Mode

1=Disabled
2=Run Enabled
3=Service Test

SYS_MODE

HVAC

Current HVAC Mode

1=Disabled
2=Ventilation
3=Cool
4=Heat

HVACMODE

HV.DN

Remote HVAC Mode Disable

No/Yes

HVACDOWN

forcible

EFF.C

Cool Setpoint In Effect

xx.x

°F

CSP_EFF

EFF.H

Heat Setpoint In Effect

xx.x

°F

HSP_EFF

OCC

Currently Occupied

No/Yes

OCCUPIED

forcible

forcible

T.OVR

Timed Override in Effect

No/Yes

MODETOVR

LINK

Linkage Active

No/Yes

MODELINK

D.LMT

Demand Limit In Effect

No/Yes

MODEDMDL

C.LOC

Compressor OAT Lockout

No/Yes

COMPLOCK

H.LOC

Heat OAT Lockout

No/Yes

HEATLOCK

OK.EC

OK to Use Economizer?

No/Yes

ECONCOOL

COOL

Cooling Status

COOLDISP

DMD.C

Cooling Demand

xxx.x

^F

COOL_DMD

AVL.C

Available Cooling Stages

x

AVLCSTGS

REQ.C

Requested Cooling Stages

x

REQCSTGS

MAX.C

Max Allowed Cool Stages

x

MAXCSTGS

forcible

LMT.C

Max Cool Stage In Effect

x

CSTGLIMT

IDF

Indoor Fan State

Off/On

IDFSTATE

F.SPD

Commanded Fan Speed

xxx

%

FANSPEED

OFC.1

Outdoor Fan 1 Relay

Off/On

OFC_1

OFC.2

Outdoor Fan 2 Relay

Off/On

OFC_2

OFC.3

Outdoor Fan 3 Relay

Off/On

OFC_3

CRC

Cool­>Reheat1 Control

Off/On

CRC

CIR.A

Refrigerant Circuit A

CIRCUIT A

CMP.A

Circuit A Compressor(s)

Off/On

COMP_A

TG.A

Timeguard A

xxx

sec

TIMGD_A

RH2.A

Reheat2 Valve A

Off/On

RH2_A

SST.A

Sat. Suction Temp A

xxx.x

°F

SST_A

SSP.A

Suction Pressure A

xxx.x

psig

SSP_A

SCT.A

Sat. Condenser Temp A

xxx.x

°F

SCT_A

SCP.A

Condenser Pressure A

xxx.x

psig

SCP_A

CIR.B

Refrigerant Circuit B

CIRCUIT B

CMP.B

Circuit B Compressor

Off/On

COMP_B

TG.B

Timeguard B

xxx

sec

TIMGD_B

RH2.B

Reheat2 Valve B,C

Off/On

RH2_B

SST.B

Sat. Suction Temp B

xxx.x

°F

SST_B

SSP.B

Suction Pressure B

xxx.x

psig

SSP_B

SCT.B

Sat. Condenser Temp B

xxx.x

°F

SCT_B

SCP.B

Condenser Pressure B

xxx.x

psig

SCP_B

CIR.C

Refrigerant Circuit C

CIRCUIT C

CMP.C

Circuit C Compressor

Off/On

COMP_C

TG.C

Timeguard C

xxx

sec

TIMGD_C

RH2.C

Reheat2 Valve B,C

Off/On

RH2_B

SST.C

Sat. Suction Temp C

xxx.x

°F

SST_C

SSP.C

Suction Pressure C

xxx.x

psig

SSP_C

SCT.C

Sat. Condenser Temp C

xxx.x

°F

SCT_C

SCP.C

Condenser Pressure C

xxx.x

psig

SCP_C

48/50PG and PM