APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — OPERATING MODES
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
OPERATING MODES
MAINTENANCE
MODE
Control Modes
MODES
SYS
Unit operation disabled
Unit operation enabled
Service test enabled
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
(table only)
HVAC
HVAC Operation Disabled
Ventilation (fanonly)
Cooling
Free Cooling
Unoccupied Free Cooling
Reheat1
Reheat2
Reheat1 / Reheat2
Heating
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
HV.DN
Remote HVAC Mode Disable
No/Yes
HVACDOWN
forcible
EFF.C
Cool Setpoint In Effect
xx.x
°F
CSP_EFF
EFF.H
Heat Setpoint In Effect
xx.x
°F
HSP_EFF
OCC
Currently Occupied
No/Yes
OCCUPIED
forcible
forcible
T.OVR
Timed Override in Effect
No/Yes
MODETOVR
LINK
Linkage Active
No/Yes
MODELINK
D.LMT
Demand Limit In Effect
No/Yes
MODEDMDL
C.LOC
Compressor OAT Lockout
No/Yes
COMPLOCK
H.LOC
Heat OAT Lockout
No/Yes
HEATLOCK
OK.EC
OK to Use Economizer?
No/Yes
ECONCOOL
COOL
Cool Mode Diagnostic
COOLDIAG
COOL
In Cooling Mode?
No/Yes
IN_COOL
OK.CL
OK to Select Cool Mode?
No/Yes
OKTOCOOL
MS.TG
Mode Select Timeguard
xxx
secs
COOLMSTG
OK.EC
OK to Use Economizer?
No/Yes
ECONCOOL
OK.MC
OK to Use Compressors?
No/Yes
MECHCOOL
C.LOC
Compressor OAT Lockout
No/Yes
COMPLOCK
CA.LO
Circuit A Lockout Temp
xxx
°F
OATLCMPA
CB.LO
Circuit B Lockout Temp
xxx
°F
OATLCMPB
CC.LO
Circuit C Lockout Temp
xxx
°F
OATLCMPC
IDF
Indoor Fan State
Off/On
IDFSTATE
F.SPD
Commanded Fan Speed
xxx
%
FANSPEED
AVL.C
Available Cooling Stages
x
AVLCSTGS
REQ.C
Requested Cooling Stages
x
REQCSTGS
LMT.C
Max Cool Stage In Effect
x
CSTGLIMT
ACT.C
Actual Cooling Stages
x
ACTCSTGS
CMP.A
Circuit A Compressor(s)
Off/On
COMP_A
CMP.B
Circuit B Compressor
Off/On
COMP_B
CMP.C
Circuit C Compressor
Off/On
COMP_C
ST.A
Circuit A Strikes
x
ASTRIKES
ST.B
Circuit B Strikes
x
BSTRIKES
ST.C
Circuit C Strikes
x
CSTRIKES
F.LEV
Outdoor Fan Level
x
FANLEV
SAT
Supply Air Temperature
SAT
Supply Air Temperature
xxx.x
°F
SAT_DISP
SA.DM
Supply Air Temp Demand
xxx.x
^F
SAT_DMD
SA.PD
SAT Cool Demand (+) Level
xx.x
^F
SAT_POS
SA.ND
SAT Cool Demand () Level
xx.x
^F
SAT_NEG
SAT.U
Minimum SAT Upper Level
xx.x
°F
SATMIN_H
SAT.L
Minimum SAT Lower Level
xx.x
°F
SATMIN_L
SA.TR
Supply Air d/dt (F/min)
xxxx.x
SATTREND
SA.DR
SAT Delta Reference Temp
xxx.x
°F
SAT_REF
SPT
Space Temperature
SPT
Space Temperature
xxx.x
°F
SPACE_T
forcible
forcible
DMD.C
Cooling Demand
xxx.x
^F
COOL_DMD
TRD.C
Cool Demand d/dt (F/min)
xxx.x
CLDTREND
CL.PD
SPT Cool Demand (+) Level
xx.x
^F
DEM_POS
CL.ND
SPT Cool Demand () Level
xx.x
^F
DEM_NEG
C.LAG
Cool Thermal Lag Factor
x.x
COOL_LAG
HMZR
Humidimizer
REHT
Humidimizer Equipped
No/Yes
REHEAT
HUM
Space Humidity Switch
Low/High
HUM_STAT
forcible
SP.RH
Space Humidity Sensor
xxx.x
%
SPRH
forcible
forcible
R.LO.A
Reheat2 OAT Lockout A
No/Yes
RHALOCK
RA.LO
Reheat2 OAT Limit A
xx
°F
OATLRH_A
R.LP.A
Reheat2 SSP Override A
No/Yes
RHALPOV
R.LO.B
Reheat2 OAT Lockout B,C
No/Yes
RHBLOCK
RB.LO
Reheat2 OAT Limit B,C
xx
°F
OATLRH_B
R.LP.B
Reheat2 SSP Override B,C
No/Yes
RHBLPOV
AVL.R
Available Reheat2 Stages
x
AVLRSTGS
REQ.R
Requested Reheat2 Stages
x
REQRSTGS
ACT.R
Actual Reheat2 Stages
x
ACTRSTGS
CRC
Cool>Reheat1 Control
Off/On
CRC
RH2.A
Reheat2 Valve A
Off/On
RH2_A
RH2.B
Reheat2 Valve B,C
Off/On
RH2_B