beautypg.com

Fan performance — 48pgd12 horizontal units – Carrier 48/50PM C16-28 User Manual

Page 136

background image

136

Fan Performance — 48PGF09 Horizontal Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2550

446

0.39

524

0.51

593

0.63

657

0.76

717

0.89

2700

464

0.45

538

0.57

605

0.70

667

0.83

726

0.97

2850

481

0.52

553

0.65

618

0.78

678

0.92

735

1.06

3000

499

0.59

569

0.72

632

0.86

690

1.01

746

1.16

3150

517

0.67

584

0.81

646

0.95

703

1.10

756

1.26

3300

535

0.75

600

0.90

660

1.05

715

1.21

768

1.37

3450

553

0.85

617

1.00

675

1.16

729

1.32

780

1.48

3600

571

0.95

633

1.11

690

1.27

742

1.44

792

1.61

3750

590

1.06

650

1.23

705

1.40

756

1.57

805

1.74

3900

608

1.18

667

1.35

720

1.53

771

1.71

819

1.89

4050

627

1.30

684

1.49

736

1.67

786

1.85

832

2.04

4200

646

1.44

701

1.63

752

1.82

801

2.01

846

2.20

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2550

774

1.04

829

1.18

881

1.33

 930

1.49

 978

1.65

2700

781

1.12

834

1.27

885

1.43

 934

1.59

 981

1.75

2850

789

1.21

841

1.37

891

1.53

 939

1.70

 985

1.87

3000

798

1.31

849

1.47

897

1.64

 944

1.81

 990

1.98

3150

808

1.42

857

1.58

905

1.75

 951

1.93

 995

2.11

3300

818

1.53

866

1.70

913

1.88

 958

2.06

1001

2.24

3450

829

1.65

876

1.83

921

2.01

 965

2.19

1008

2.38

3600

840

1.78

886

1.96

931

2.15

 974

2.34

1016

2.53

3750

852

1.92

897

2.11

941

2.30

 983

2.49

1024

2.69

3900

864

2.07

908

2.26

951

2.46

 993

2.65

1033

2.86

4050

877

2.23

920

2.42

962

2.62

1003

2.83

1042

3.03

4200

890

2.40

933

2.60

974

2.80

1013

3.01

1052

3.22

LEGEND
Bhp -
Brake Horsepower

High Range Motor/Drive Required

NOTES:

1. Motor drive range is 568 to 771 rpm for low range motor/drive and 812 to 1015 rpm
for high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 2.40 for low range motor/drive and 3.70 for high range
motor/drive.
3. See General Fan Performance Notes.

Fan Performance — 48PGD12 Horizontal Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3000

502

0.60

571

0.73

634

0.87

693

1.01

748

1.16

3200

525

0.70

592

0.85

652

0.99

709

1.14

762

1.30

3400

549

0.82

613

0.97

671

1.13

726

1.29

777

1.45

3600

573

0.95

634

1.11

691

1.28

743

1.44

793

1.61

3800

597

1.10

656

1.27

711

1.44

762

1.62

810

1.79

4000

621

1.26

678

1.44

731

1.62

781

1.80

828

1.99

4200

645

1.43

700

1.62

752

1.81

800

2.00

846

2.20

4400

669

1.62

723

1.83

772

2.02

819

2.22

864

2.42

4600

694

1.83

745

2.04

794

2.25

839

2.46

883

2.67

4800

719

2.06

768

2.28

815

2.50

860

2.71

902

2.93

5000

743

2.30

791

2.53

837

2.76

880

2.98

922

3.21

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3000

800

1.32

 851

1.48

 899

1.64

 946

1.82

 992

1.99

3200

813

1.46

 862

1.63

 909

1.80

 955

1.98

 999

2.16

3400

827

1.62

 874

1.79

 920

1.97

 964

2.15

1007

2.34

3600

841

1.79

 887

1.97

 932

2.15

 975

2.34

1017

2.53

3800

857

1.97

 901

2.16

 945

2.35

 986

2.55

1027

2.75

4000

873

2.18

 916

2.37

 958

2.56

 999

2.77

1039

2.97

4200

889

2.39

 932

2.59

 973

2.80

1013

3.00

1051

3.22

4400

907

2.63

 948

2.83

 988

3.04

1027

3.26

1065

3.48

4600

925

2.88

 965

3.09

1004

3.31

1042

3.53

4800

943

3.15

 982

3.37

1020

3.59

5000

962

3.44

1000

3.67

LEGEND
Bhp -
Brake Horsepower

High Range Motor/Drive Required

NOTES:

1. Motor drive range is 690 to 893 rpm for low range motor/drive, 852 to 1055 rpm for
high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 3.10 for low range motor/drive and 3.70 for high range
motor/drive.
3. See General Fan Performance Notes.

48/50PG and PM