SERVICE TEST

The Service Test function can be used to verify proper operation of
compressors, heating stages, Humidi−MiZer

t System, indoor fan,

outdoor fans, power exhaust fans, economizer, crankcase heaters,
and the alarm relay. Use of Service Test is recommended at initial
system start up and during troubleshooting (See Table 4 for point
details).

Service Test mode has the following changes from normal
operation:

S Outdoor air temperature limits for cooling circuits, economizer,

and heating are ignored. Normal compressor time guards and
other staging delays are reduced to 30 seconds or less.

S Circuit alerts are limited to 1 strike (versus 3) before changing to

alarm shut down state.

S The status of ALM.N is ignored so all alerts and alarms are

broadcast on CCN.

S The words “SERVICE TEST” are inserted into every alarm

message.

Service test can only be turned ON/OFF at the unit display. Once
turned ON, other entries may be made with the display or through
CCN. To turn Service Test on, change the value of TEST to ON.
To turn service test off, change the value of TEST to OFF.

NOTE: Service Test mode may be password protected. Refer to
Basic Control Usage section for more information. Depending on
the unit model, factory−installed options, and field−installed
accessories, some of the Service Test functions may not apply.

Independent Outputs

The independent (INDP) submenu is used to change output status
for the economizer, power exhaust stages, crankcase heaters, alarm
relay, and outside air unit.. These independent outputs can operate
simultaneously with other Service Test modes. All outputs return to
normal operation when Service Test is turned off. When the
economizer is using the factory default Digital Control Type
(Configuration

ECONE.CTL is 1 or 2) then the Economizer

Calibration feature may be used to automatically check and reset
the economizer actuator range of motion. Refer to the economizer
operation section of more details. On EnergyX equipped units, use
the outside air unit (OAU) points to test the ERV components.

Fan Test

The fans (FANS) submenu is used to change output status for the
indoor fan and outdoor fan stages. Indoor fan speed test (F.SPD) is
only available for use when adaptive fan is configured
(Configuration

A.FANAF.EN) for Yes. F.SPD runs the fan at

the desired speed entered. Units with Humidi−MiZer systems have
limited or no manual outdoor fan control from test mode.

Cooling Test

The cooling (COOL) submenu is used to change output status for
the individual compressors. Compressor starts are staggered by 15
seconds. The fans (FANS) and heating (HEAT) service test outputs
are reset to OFF for the cooling service test. Indoor fans and
outdoor fans are controlled normally to maintain proper unit
operation. If adaptive fan is configured, then the indoor fan speed
will default to the Mech. Cooling Fan Speed configuration point
(Configuration

A.FANFS.CL) when one compressor is

turned on. The Reduced Cool Fan Speed (F.SPD) can only be
changed while one stage is running. If more then one stage is on
the actual fan speed will be 100%. F.SPD shows the reduced speed
not actual speed. On single stage units, actual fan speed will be
100% when the compressor is on. All normal cooling alarms and
alerts are functional.

When charging unit, all outdoor fans may be forced on in cooling
service test modes by setting the Outdoor Fan Override (OF.OV) to
on.

NOTE: Circuit A is always operated with Circuit B and/or C in
Humidi-MiZer

 system equipped units.

Humidi−MiZer

t Test

For units with the factory Humidi-MiZer

 option, the

Humidi-MiZer (HZMR) submenu is used to change the output
status to operate the circuits in different Humidi−MiZer modes or
to separately test the Humidi−MiZer valve operations. Refer to the
Humidi-MiZer operation section for details on these modes and
valves. The fans (FANS), cooling (COOL), and heating (HEAT)
service test outputs are reset to OFF for the Humdi−MiZer service
test. Indoor and outdoor fans are controlled normally to maintain
proper unit operation. If adaptive fan is configured, then the indoor
fan speed will default to the Reheat2 Fan Speed configuration
point (Configuration

A.FANFS.RH) when Reheat2 test is

turned on. The Reheat2 fan speed (F.SPD) only reflects the speed
setting for testing Reheat2 circuits, and can only be changed when
a circuit is in Reheat2. Actual speed may be different if Reheat 1
tests are being performed. All normal cooling alarms and alerts are
functional. Refer to the Humidi−MiZer operating section for more
information.

NOTE: Circuit A is always operated with Circuit B and/or C in
Humidi-MiZer system equipped units.

Table 4 – Service Test Modes and Submodes Directory

DISPLAY MENU/
SUB-MENU/
NAME

EXPANDED NAME

VALUES

SERVICE TEST

TEST

Field Service Test Mode

Off/On

INDP

Test Independent Outputs

ECON

Economizer Position Test

0 to 100

E.CAL

Calibrate Economizer

Off/On

PE.1

Power Exhaust 1 Test

Off/On

PE.2

Power Exhaust 2 Test

Off/On

ALRM

Alarm Relay Test

Off/On

CCH

Crankcase Heat Test

Off/On

OA.DM

OAU 2­position Damper

Close/Open

WHL

OAU Wheel Test

0 to 100

OA.OF

OAU OA Fan Speed Test

0 to100

OA.XF

OAU PE Fan Speed Test

0 to100

OA.HT

OAU Tempring Heater Test

0 to 100

FANS

Test Fans

IDF

Indoor Fan Power Test

Off/On

F.SPD

Indoor Fan Speed Test

0 to 100

OFC.1

Outdoor Fan 1 Test

Off/On

OFC.2

Outdoor Fan 2 Test

Off/On

OFC.3

Outdoor Fan 3 Test

Off/On

COOL

Test Cooling

CMP.A

Cool A Test

Off/On

CMP.B

Cool B Test

Off/On

CMP.C

Cool C Test

Off/On

F.SPD

Reduced Cool Fan Speed

60 to 100

OF.OV

Outdoor Fan Override

Off/On

HMZR

Test Humidi-MiZer

RH1.A

Reheat1 A Test

Off/On

RH1.B

Reheat1 B Test

Off/On

RH1.C

Reheat1 C Test

Off/On

RH2.A

Reheat2 A Test

Off/On

RH2.B

Reheat2 B Test

Off/On

RH2.C

Reheat2 C Test

Off/On

F.SPD

Reheat2 Fan Speed

65 to 100

CRC

Cool­>Reheat1 Valve Test

Off/On

RHV.A

Reheat2 Valve A Test

Off/On

RHV.B

Reheat2 Valve B,C Test

Off/On

HEAT

Test Heating

HT.1

Heat Stage 1 Test

Off/On

HT.2

Heat Stage 2 Test

Off/On

F.SPD

Reduced Heat Fan Speed

65 to 100